background image

GB

15

Recessing the insert

When recessing the insert, adjacent walls that are not classed as fire walls 
or are considered unsuitable for exposure to heat must be protected by 
non-combustible building material in accordance with the specifications 
below.
All joints on the non-combustible material must be sealed using the method 
recommended by the manufacturer. The space between the insert and the 
recess must be ventilated in accordance with specifications/dimensions 
diagrams.
Please refer to the manufacturer’s installation instructions when connecting 
a steel chimney to a top outlet. Observe the requirements for the safe 
distance from the steel chimney to combustible materials. Because of the 
strong heat radiating from the door, combustible materials must be placed a 
minimum of 1,4 m from the door.
The insert must be installed with clearance to the building material, not in 
direct contact with it, to allow for thermal expansion of the insert.

Material requirements

The building material must not be combustible.
The thermal conductivity coefficient 

λ 

must be maximum 0.14 W/mK.

The building material must always be at least 100 mm thick.
Where the insulation properties of building material are given as a U-value, it 
must be maximum 1.4 W/ m²K.

List of suitable materials:
Aerated concrete: 

λ

= 0.12–0.14

Vermiculite: 

λ

= 0.12–0.14

Calcium silicate: 

λ

= 0.09

Sealing

The recess must not go all the way up to the ceiling, leave an air gap of at 
least 20 mm closest to the ceiling. The recess must be sealed off above the 
convection exhaust. The seal must be 100 mm above the convection exhaust’s 
upper edge and must be made of 40 mm non-flammable material according 
to the material requirements above. Use heat-resistant silicone, for example, 
between the seal and chimney. 

Convection air

The convection air ventilates the surround, cools the insert and carries hot 
air out into the room. The total sum of the effective cross-section area up 
and down must not be less than the stated values. The air intake must be 
positioned somewhere between floor level and the bottom of the insert, at 
the front or on the sides of the recess. The air exhaust must be positioned 
above the highest point of the insert at the front or the sides of the recess.
If the air intakes or exhausts are positioned on the sides, the areas for the 
left and right side respectively must be the same size to ensure that the 
insert is evenly cooled.
Check the minimum distance to the ceiling.

Convection air in: 200 cm²
Convection air out: 200 cm²

Floor and load-bearing base

Combustible flooring beneath the insert must be protected. The examples 
show the floor protected by a 40 mm calcium silicate board.
Ensure that the convection box is placed on a base strong enough to bear the 
weight of the stove and chimney.
The base must not block the flow of convection air in the space between the 
insert and recess.

Steel chimney on the insert

If the insert is to be connected to a module-based steel chimney, it must be 
connected via a chimney support panel (accessory). The weight of the steel 
chimney on the insert with the chimney support panel must be maximum
100 kg.

Summary of Contents for Contura Ci2

Page 1: ...Ci2 Ci2G contura eu ...

Page 2: ...30 Montage 32 Fakta 3 Prestandadeklaration 4 EU försäkran om överrensstämmelse 5 Måttskiss 6 Inbyggnadsexempel 8 Montering 32 Fakta 18 Ytelseserklæring 19 EU samsvarserklæring 20 Målskisse 21 Innbyggingseksempel 23 Montering 32 Facts 10 Declaration of performance 11 EU Declaration of Confirmit 12 Dimensions diagram 13 Recess example 15 Assembly 32 ...

Page 3: ...ed Also read the Lighting instructions before lighting for the first time The insert becomes very hot During operation certain surfaces of the insert become very hot and can cause burn injury if touched Be aware of the strong heat radiated through the hatch glass Placing flammable material closer than the safe distance indicated may cause a fire Pyre lighting can cause quick gas ignition with the ...

Page 4: ...assification A1 Minimum distance to flammable materials Rear 200 mm Side 250 mm Ceiling 1200 mm Ceiling 700 mm front grate Front 1400 mm Floor 275 mm Fire hazard due to burning fuel falling out Pass EN 13229 2001 A2 2004 AC 2007 Cleanability Pass Emissions from combustion CO 1500 mg Nm3 13 O2 Surface temperatures Pass Temperature on the handle Pass Mechanical resistance Pass Temperature in the spa...

Page 5: ...ture control No In standby mode elSB kW With mechanic thermostat room temperature control No With electronic room temperature control No With electronic room temperature control plus day timer No With electronic room temperature control plus week timer No OTHER CONTROL OPTIONS Room temperature control with presence detection No Room temperature control with open window detection No With distance c...

Page 6: ...ements must be at least 1 4 metre from the front of the insert door When connecting to a steel chimney the requirements for safe distance to the chimney must also be observed A clearance of at least 300 mm must be allowed as a safe distance between an uninsulated flue pipe and com bustible building elements Dimensions diagram 3 sided frame 4 sided frame ...

Page 7: ...nce must stand on a constructional hearth which meet the building regulations and has minimum dimension as shown in the diagram Always check that the building has enough bearing capacity for the heart stove and chimney The stove can be loaded with maximum 100 kg of chimney ...

Page 8: ...t to the ceiling The recess must be sealed off above the convection exhaust The seal must be 100 mm above the convection exhaust s upper edge and must be made of 40 mm non flammable material according to the material requirements above Use heat resistant silicone for example between the seal and chimney Convection air The convection air ventilates the surround cools the insert and carries hot air ...

Page 9: ...t be a 20 mm air space between the building board and the combustible wall The air space must allow air to flow freely along the lower and upper edges see diagram to the right Diagram of aerated wall Two calcium silicate board battens ensure that the air space is maintained Firewall approved and fully complies with safety requirements according to the authorised inspection body Examples of approve...

Page 10: ...Air gap 550 40 30 275 1100 100 Area in min 300 cm2 Load bearing base Area out min 200 cm2 Combustible wall 700 min 100 20 40 40 55 100 275 1100 Area out min 200 cm2 Area in min 300 cm2 Heat shield Load bearing base 20 mm Air gap max 100 Ci2 Recess example Always observe the safety distances to combustible material required by a steel flue The dimensions are the minimum dimensions unless otherwise ...

Page 11: ...port 2 Fire bricks Vermiculite 3 Type plate 4 Grate 5 Ash pan 6 Hearth base 7 Serial number Før montering Montage Hvis innsatsen må legges ned for å flyttes bør løse deler demonteres Demontering av brennplater og hvelv er beskrevet på neste side 1 Stussplate 2 Brennplater og hvelv Vermikulitt 3 Typeskilt 4 Rist 5 Askeskuff 6 Ildstedsbunn 7 Serienummer Les éléments non fixés devront être déposés si...

Page 12: ...33 1 2 3 5 6 7 4 Handle with care ...

Page 13: ...eas This when burning wood logs and operated in accordance with these instructions and when fitted with a permanent stop to prevent closure of the air control unit beyond 31 open position Mandatory for smoke control areas The permanent stop must be installed if the appliance is to be used in a smoke control area this stop must not be removed in smoke control areas otherwise an offence will be comm...

Page 14: ...35 8 9 10 ...

Page 15: ...36 11 12 ...

Page 16: ...ara minst 10 mm luftspalt detta pga insatsens värmeutvidgning The insert is designed to be installed as a stove cassette in existing approved open hearths There must be an 10 mm air gap around the insert to allow for the expansion of the insert when hot L insert peut être installé comme une cassette dans un foyer ouvert existant et homologué Un espace d au moins 10 mm doit être prévu autour de l i...

Page 17: ...38 Accessory Tilbehør Accessoire Tillbehör GB NO FR SE 1 2 3 ...

Page 18: ...nnsatsen kan også kobles til med faste rør som føres opp i skorsteinen Raccordement à une cheminée de maçonnerie existante Pour simplifier le montage il est recommandé d utiliser un tuyau flexible proposé en option Fixez le manchon dans le tuyau Raccordez et scellez entre le tuyau et la cheminé selon les instructions séparées L insert peut également être raccordé avec des conduits fixes dans la ch...

Page 19: ...40 3 4 ...

Page 20: ...41 x4 5 x4 6 ...

Page 21: ...42 7 mm 7 8 ...

Page 22: ...43 9 10 ...

Page 23: ...44 11 12 ...

Page 24: ... de invändiga delarna i omvänd ordning Reinstall the internal components in reverse order Sett de innvendige delene tilbake på plass i motsatt rekkefølge Remontez les éléments intérieurs dans l ordre inverse SE GB NO FR ...

Page 25: ......

Page 26: ......

Page 27: ......

Page 28: ...811483 IAV SE EX Ci2 2 2022 05 24 NIBE AB Box 134 285 23 Markaryd Sweden contura eu ...

Reviews: