Fire alarm type 1
■
The exhaust air damper (QM40) closes
■
The fire bypass damper (QM41) opens
■
Exhaust air fan (GQ2) runs at fixed fire flow, which is
set in menu 5.3.22.
Fire alarm type 2
■
Exhaust air fan (GQ2) stops
■
The exhaust air damper (QM40) closes
fire alarm temperature BT20
Make settings here for the speed at which the fan will
run in the event of fire.
Setting range: 38–45%
Factory setting: 38%
fan speed during fire alarm
Make settings here for the speed at which the fan will
run in the event of fire.
Setting range: 0–100%
Factory setting: 70%
filt. alarm press.
Make settings for alarm for a clogged filter here. When
the set value is exceeded, an alarm is triggered.
Setting range: 100–300 Pa
Factory setting: 150 Pa
Menu 5.6 - forced control
You can make the settings for forced control of Green-
Master-HP here. Forced control must only be used by
users with a good knowledge of the system. When forced
control is activated, the alarm functions are disabled.