General
All internal electrical equipment is connected at the
factory. External connections have to be connected ac-
cording to the applicable unit specification.
■
Disconnect the air treatment unit before insulation
testing the house wiring.
■
If the building is equipped with an earth-fault breaker,
GreenMaster-HP should be equipped with a separate
one.
■
If a miniature circuit breaker is used, this has to have
at least motor characteristic “C”. See the enclosed unit
specification for fuse size.
■
Communication and sensor cables to external connec-
tions must not be laid close to high current cables.
■
The minimum area of communication and sensor
cables to external connections must be 0.5 mm² up to
50 m, for example EKKX or LiYY or equivalent.
■
When routing a cable in GreenMaster-HP, cable
grommets must be used. Secure the cables in the
grooves in the bottom section of the distribution box.
NOTE
The switch (SF1) must not be set to " " or "
"
until the heating medium circuit has been
filled. Components in the product could be
damaged.
NOTE
Electrical installation and service must be car-
ried out under the supervision of a qualified
electrician. Cut the current with the circuit
breaker before carrying out any servicing.
Electrical installation and wiring must be car-
ried out in accordance with the stipulations in
force.
NOTE
Check the connections, main voltage and phase
voltage before the machine is started, to pre-
vent damage to the air treatment unit’s elec-
tronics.
Miniature circuit-breaker
The air treatment unit’s operating circuit and some of
its internal components are fused internally by a mini-
ature circuit breaker (FC1).
Accessibility, electrical connection
The plastic cap of the electrical boxes is opened using a
screwdriver.
NOTE
The cover for the input card is opened without
a tool.
Removing the cover, input circuit board
1. Unscrew the screws and angle out the cover.
LEK
LEK
LEK
LEK
2. Pull off the cover.
LEK
LEK
LEK
LEK
Removing the hatch, electrical cabinet
1. Disconnect the contacts.
LEK
2. Unscrew the screws and angle out the cover.
LEK
LEK
LEK
LEK
23
Chapter 5 |
Electrical connections
GreenMaster-HP
5 Electrical connections