General
Pipe and ventilation installation has to be performed
according to applicable regulations.
GreenMaster-HP can operate with a return temperature
of up to approx. 58 °C and an outgoing temperature of
65 °C.
GreenMaster-HP is not equipped with external shut off
valves; these should be installed to facilitate any future
servicing. In addition, non-return valves and particle fil-
ters should be installed.
GreenMaster-HP when placed indoors, is equipped with
sheet metal guide connections for exhaust air and extract
air ducts. When located outdoors, GreenMaster-HP is
equipped with sheet metal guide connection for exhaust
air duct and ventilation grille on the extract air side.
Rectangular duct connections are standard on all models
of GreenMaster-HP. Connection dimensions for guide
connections can be found in the relevant unit specifica-
tion for the installed unit.
NOTE
The pipe systems have to be flushed clean be-
fore GreenMaster-HP is connected, to prevent
any contaminants from damaging the compon-
ents.
NOTE
Do not solder directly on the pipes in GreenMas-
ter-HP, because of internal sensors.
Compression ring coupling alternatively pres-
sure connection should be used.
NOTE
The heating system's pipes must be earthed to
prevent a potential difference between them
and the building's protective earth.
NOTE
The potential to clean the air ducts in the future
is required.
Ventilation flow
The ventilation flow must comply with the applicable
national standards.
Connect the property’s common exhaust air duct with
the guide connection to the unit’s filter side.
If flue gas extraction is required, an extra air duct with a
bypass damper has to be installed and connected to the
unit’s prepared fan-in-operation connection.
Adjusting ventilation
In order to achieve the necessary air exchange in the
property, the correct adjustment of the air flow in the
air treatment unit is required.
As soon as possible after installation, the ventilation
should be adjusted to ensure the air flow is set according
to the planned value for the property. Incorrect adjust-
ment can result in impaired function, recovery and
comfort.
System diagram
GreenMaster-HP consists of cooling module, circulation
pumps, air treatment unit and control system with pos-
sibility of additional heat. GreenMaster-HP is connected
to heating medium circuit.
Explanation
Air treatment section
AZ1
Air flow function
BF2
Differential pressure sensor, exhaust air
duct
BP12
Differential pressure sensor, air filter
BP13
Differential pressure sensor, fan
BP14
Differential pressure sensor, heat ex-
changer
BP15
Exhaust air sensor
BT20
Extract air sensor
BT21
Exhaust air fan
GQ2
Venting valve, brine side
QM21
Heat exchanger
EP16
Heat pump system
EB100
Level monitor
BL1
Manometer, brine side
BP6
Temperature sensor, outdoor
BT1
Expansion vessel, closed, brine side
CM3
Cooling module
EP14
Safety valve, brine
FL3
Tapping valve
QM3
Tapping valve
QM4
Venting valve, brine side
QM21
Vent valve, heat exchanger
QM24
Shut off valve, brine flow
QM33
Shut off valve, brine return
QM34
Shut-off valve, heating medium flow
QM42
Shut off valve, heating medium return
QM43
Shut-off valve, heating medium side
QM54 - QM55
Filler valve/Filterball
QZ2
Non-return valve
RM10 - RM12
Connection, filling brine
XL27, XL28
19
Chapter 4 |
Pipe and ventilation connections
GreenMaster-HP
4 Pipe and ventilation connections