20
HK 200S
HK 200S-6
Temperature limiter (F3) is accessible behind the front
cover. Temperature limiter is reset by strong press-
ing of the button (F3-SF2) using a small screwdriver.
Press the button, max. 15 N (approx. 1.5 kg).
Resetting
Cable blockade
Use an appropriate tool to release/block cables in the
internal module clamps.
The power supply is to be connected to clamp (X2)
via the input at the back of the unit. The cable must be
dimensioned according to the applicable standards.
HK 200S-6 / HK 200S must be connected to the
power supply 400 V 3N AC 50Hz as specifi ed on the
clamp (X2).
Connection
Connections
IMPORTANT
In order to prevent interferences, do not lay unshielded
communication and/or signal cables to external con-
tacts at the distances lower than 20 cm from high-
voltage cables.
Power supply connection
Temperature limiter
Temperature limiter (F3) cuts off the power supply of
the electrical heating module if the temperature in-
creases to the range of approximately 87 °C, and can
be reset manually.
F3
F3-SF2
EMER
GENC
Y
SMO
SMO
AMS 10-6
Circuit breaker
The system for automatic regulation of the heating,
circulation pump, and their cabling at HK 200S / HK
200S-6 are secured internally with a circuit breaker
(F2). The external AMS 10 module and peripheries
are secured internally at HK 200S / HK 200S-6 with
a circuit breaker (F1).
Chapter 5 |
Electrical connections
2
1
3
L1
L
L2 L3 N N PE
Remove the bridge
for double tariff
control
Remove the bridge
for double tariff
control