Appendix B
5B Series Module Data Sheets
©
National Instruments Corporation
B-19
SC-2311 User Manual
1
Includes the combined effects of repeatability, hysteresis, and conformity error. Loads heavier than 50
k
will degrade conformity and gain temperature coefficient.
2
The user's board layout must separate Power Common from Output Common. When the output
switch is not used, connect the Enable Input to the Output Common. Output Common is connected to
power common when the 5B35 is installed on a
5B Series backplane
.
Specifications subject to change without notice.
Copyright 1995-2000
Analog Devices, Inc.
All rights reserved.
Environmental
Temperature Range
Rated Performance
-40˚C to +85˚C
Operating
-40˚C to +85˚C
Storage
-40˚C to +85˚C
Relative Humidity
0 to 93% @ +40˚C noncondensing
RFI Susceptibility
±0.5% Span error @ 400 MHz, 5 Watt, 3 ft
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com