FP-AIO-600 and cFP-AIO-600
6
ni.com
Note
The input and output channels of the
[c]FP-AIO-600 are
not
electrically isolated from
each other.
Figure 4 shows the input circuitry on a single input channel.
Figure 4.
Input Circuitry on One Channel of the [c]FP-AIO-600
Voltage Inputs
The input ranges for voltage signals are
5,
10,
15,
30, 0–5,
0–10, 0–15, and 0–30 V. FieldPoint software accounts for the
20% overranging feature and shows the ranges accordingly.
Figure 5 shows how to connect a voltage source without an
external power supply to one input channel of the [c]FP-AIO-600.
Figure 5.
Voltage Input without an External Power Supply
Filter
12-Bit
ADC
V
SUP
V
IN
COM
I
IN
V
C
To Next Channel
105
Ω
1.5 M
Ω
V
SUP
V
IN
V
C
To Analog
Input Circuitry
To Next Channel
1.5 M
Ω
Input
Impedance
COM
[c]FP-AIO-600
Voltage
Source
+
–
I
IN
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com