National Instruments Corp.
15
FP-AIO-600 and cFP-AIO-600
Current Outputs
Output range ..................................... 0–20 or 4–20 mA,
programmable
(0–21 or 3.5–21 mA
with overranging)
Type .................................................. Current source, external
power required
External power supply ...................... 10
–
30 VDC, 125 mA for
4 output channels
Internal voltage drop......................... 3 V
Resistive load .................................... Up to 1 k
with 24 V
power supply
1
Protection.......................................... Short-circuit and
open-circuit
Default power-up state...................... 0 mA
Current output accuracy by current output range
Dynamic Characteristics
Hardware update rate ........................ 1,700 updates/s
Slew rate ........................................... 0.4 mA/
s
Physical Characteristics
Indicators .......................................... Green
POWER
and
READY
indicators, and
4 red output indicators
Weight
FP-AIO-600................................ 141 g (4.9 oz)
cFP-AIO-600 .............................. 111 g (3.9 oz)
1
Maximum load resistance
= (
Supply voltage
–
Internal voltage drop
)/0.021 A
Current Output
Range (with
Overranging)
Accuracy
at 15 to 35
°
C
(% of Output Value;
% of Full Scale)
Accuracy
at – 40 to 70
°
C
(% of Output Value;
% of Full Scale)
0–21 mA
0.03%;
0.13%
0.14%;
0.2%
3.5–21 mA
0.03%;
0.16%
0.14%;
0.23%
Artisan Technology Group - Quality Instrumentation ... Guaranteed | (888) 88-SOURCE | www.artisantg.com