41
11.3 Recommended Wire Gauge Selection Table
Table 23
Model Sectional
Area
Temperature Conditions
AWG
mm²
60
℃
75
℃
85
℃
90
℃
Wire
model:
RUW, T ,
UF
Wire
model:
RHW, RH
Wire model: V,
MI
Wire
model:
TA, TBS, SA, AV
Rated Current (A)
14
2.08
20
20
20
20
12
3.31
25
25
30
30
10
5.26
30
35
40
40
8
8.36
40
50
55
55
6
13.3
55
65
70
75
4
21.1
70
85
95
95
3
26.7
85
100
110
110
2
33.6
95
115
125
130
1
42.4
110
130
145
150
0
53.5
125
150
165
170
00
67.4
145
175
190
195
000
85
165
200
215
225
0000
107
195
230
250
260
11.4 Trouble Shooting
Screen does not work after power-on.
Table 24
Fault
Possible Causes
Solutions
N36100 screen does not
work after power-on.
The power cord is
broken.
Change a new power cord.
The power cord is not
properly connected.
Ensure proper connection.
No output.