MS-2102
6.3
Chapter 6
Setpoint Values
MESSAGE NO:
S1-05
APPLIES TO:
Selected Heater
DEFAULT VALUE: 5°C
VALUE RANGE: -50 to 500 °C, off
41°F
-58 to 932 °F, off
DISPLAY MODE:
All
RESTRICTIONS: Heater Setpoint must not be
off
.
This function sets the Low Temperature Alarm setpoint.
It must be less than the
Heater Setpoint
. To disable this alarm, set the value to
off
. When the Heater Control
Temperature is less than or equal to this setpoint, the Low Temperature Alarm is
activated and a
LOW TEMPERATURE ALARM
message is added to the System
Status messages. The alarm deactivates when the temperature rises above this alarm
setpoint.
MESSAGE NO:
S1-06
APPLIES TO:
Selected Heater
DEFAULT VALUE: off
VALUE RANGE: -50 to 500 °C, off
-58 to 932 °F, off
DISPLAY MODE: All
RESTRICTIONS: Heater Setpoint must not be
off
.
This function sets the High Temperature Alarm setpoint.
It must be greater than the
Heater Setpoint.
To disable this alarm, set the value to
off
. When the Heater Control
Temperature is greater than or equal to this setpoint, the High Temperature Alarm is
activated and a
HIGH TEMPERATURE ALARM
message is added to the System
Status messages. The alarm deactivates when the temperature falls below this alarm
setpoint.
MESSAGE NO:
S1-07
APPLIES TO:
Selected Heater
DEFAULT VALUE: off
VALUE RANGE: 0.5 to 30.0/100.0 A, off
DISPLAY MODE: All
RESTRICTIONS: None
This function sets the Low Current Alarm setpoint.
It must be less than the High
Current Alarm setpoint.
To disable this alarm, set the value to
off
. When the Heater
Current is less than or equal to this setpoint, the Low Current Alarm is activated and
a
LOW CURRENT ALARM
message is added to the System Status messages. The
alarm deactivates when the Heater Current rises above this alarm setpoint. The value
range is in 0.5 A increments.
Note: This setpoint is based on the heater at 100% power. If Proportional Control
or Power Limit is enabled, all current measurements will be converted to 100%
power, based on a constant resistive load, before being compared to the alarm
setpoint.
MESSAGE NO:
S1-08
APPLIES TO:
Selected Heater
DEFAULT VALUE: off
VALUE RANGE: 0.5 to 30.0/100.0 A, off
DISPLAY MODE:
All
RESTRICTIONS: MS2102-1TXHx panel
This function sets the phase B: Low Current Alarm setpoint.
It must be less than the
phase B: High Current Alarm setpoint.
To disable this alarm, set the value to
off
.
When the phase B: Heater Current is less than or equal to this setpoint, the phase B:
Low Current Alarm is activated and a
B: LOW CURRENT ALARM
message is added
to the System Status messages. The alarm deactivates when the phase B: Heater
Current rises above this alarm setpoint. The value range is in 0.5 A increments.
Note: This setpoint is based on the heater at 100% power. If Proportional Control
or Power Limit is enabled, all current measurements will be converted to 100%
power, based on a constant resistive load, before being compared to the alarm
setpoint.
LOW TEMPERATURE
ALARM: 120°C
HIGH TEMPERATURE
ALARM: 130°C
B: LOW CURRENT
ALARM: 10.5A
LOW CURRENT
ALARM: 10.5A