Figure 4: FP1 Limit Setting
CXM PCB
JW3-FP1
jumper should
be clipped for
low temperature
operation
Field Supplied
Disconnect Switch
Heat Pump
A
Room Thermostat
B
A= Two power wires on single-phase units: three power
wires on three-phase units. B= 1 heat /1 cool /manual
or Auto Change-over remote 24V thermostat. Note: All
customer-supplied wiring to be copper only and must
conform to NEC and local electrical codes. Wiring
shown with dashed lines must be field-supplied and
field-installed. "B" only required with systems employing
remote mounted thermostats.
Figure 3: Typical Field Installed Wiring
WARNING!
To avoid possible injury or death due to
electrical shock, open the power supply disconnect switch
and secure it in an open position during installation.
CAUTION!
Use only copper conductors for field installed
electrical wiring. Unit terminals are not designed to accept other
types of conductors.
�
WARNING!
�
�
CAUTION!
�
Low Water Temperature Cutout Setting
CXM or DXM Control
When antifreeze is selected, the FP1 jumper (JW3) should
be clipped to select the low temperature (antifreeze 13°F
[-10.6°C]) set point and avoid nuisance faults (see “Low
Water Temperature Cutout Selection” in this manual). NOTE:
Low water temperature operation requires extended range
equipment.
Electrical - Line Voltage