Electrical - Line Voltage
Electrical - Line Voltage
All field installed wiring, including electrical ground,
must comply with the National Electrical Code as well
as all applicable local codes. Refer to the unit electrical
data for fuse sizes. Consult wiring diagram for field
connections that must be made by the installing (or
electrical) contractor.All final electrical connections must
be made with a length of flexible conduit to minimize
vibration and sound transmission to the building.
WARNING!
To avoid possible injury or death due to
electrical shock, open the power supply disconnect switch
and secure it in an open position during installation.
CAUTION!
Use only copper conductors for field installed
electrical wiring. Unit terminals are not designed to accept other
types of conductors.
�
WARNING!
�
�
CAUTION!
�
General Line Voltage Wiring
Be sure the available power is the same voltage and
phase shown on the unit serial plate. Line and low
voltage wiring must be done in accordance with local
codes or the National Electric Code, whichever is
applicable.
Power Connection
Line voltage connection is made by connecting the
incoming line voltage wires to the “L” side of the
contactor. Consult Tables 4 through 5 for correct fuse
size.
208 Volt Operation
All commercial 208-230 Volt units are factory wired for
208 Volt operation. The transformer may be switched
to the 230V tap as illustrated on the wiring diagram by
switching the red (208V) and the orange (230V) wires at
the contactor terminal.
Table 4: CCE Electrical Data
Model
Voltage
Code
Voltage
Min/Max
Voltage
Compressor
Fan
Motor
FLA
Total
Unit
FLA
Min
Circuit
Amps
Max
Fuse/
HACR
QTY
RLA
LRA
CCE07
A
115/60/1
104-126
1
7.1
46.5
0.50
7.6
9.3
15
CCE07
G
208-230/60/1
197-254
1
3.7
19.0
0.33
4.0
5.0
15
CCE07
E
265/60/1
239-292
1
2.8
16.0
0.35
3.1
3.8
15
CCE09
A
115/60/1
104-126
1
9.0
46.5
1.30
10.3
12.5
20
CCE09
G
208-230/60/1
197-254
1
4.7
23.0
0.50
5.2
6.3
15
CCE09
E
265/60/1
239-292
1
3.8
16.0
0.50
4.3
5.3
15
CCE12
A
115/60/1
104-126
1
10.6
63.0
1.30
11.9
14.6
25
CCE12
G
208-230/60/1
197-254
1
6.1
29.0
0.50
6.6
8.1
15
CCE12
E
265/60/1
239-292
1
4.8
21.6
0.50
5.3
6.5
15
CCE15
G
208-230/60/1
197-254
1
7.0
33.2
1.10
8.1
9.8
15
CCE15
E
265/60/1
239-292
1
5.4
29.0
1.00
6.4
7.8
15
CCE19
G
208-230/60/1
197-254
1
7.7
38.0
1.10
8.8
10.7
15
CCE19
E
265/60/1
239-292
1
5.8
29.0
1.00
6.8
8.2
15