7 - ADVANCED PROGRAMS
7.1 VIEWING THE DOOR STATUS ON THE APP
To display the status of the door (open, closed, partially open) on the app, you must connect the contacts to the control
unit.
The control unit can work with:
-
two normally closed contacts with no voltage
typically this means there are two micro limit switches, one for when the door opens and one for when it closes,
connected to the relevant inputs (terminals 6, 7 and 8). When the door touches the microswitch, the contact must open;
this turns on the green light in the app.
-
two normally open contacts with no voltage
typically this means there are two micro limit switches, one for when the door opens and one for when it closes,
connected to the relevant inputs (terminals 6, 7 and 8). When the door touches the microswitch, the contact must close;
this turns on the green light in the app.
-
one normally closed contact with no voltage when opening
typically this means there is one micro limit switch for when the door opens, connected to the relevant input (terminal 6,
7). When the door touches the microswitch, the contact must open; this turns on the green light in the app and turns off
the other light.
-
one normally open contact with no voltage when opening
typically this means there is one micro limit switch for when the door opens or closes, connected to the relevant input
(terminal 6, 7). When the door touches the microswitch, the contact must close; this turns on the green light in the app
and turns off the other light.
-
one normally open contact with 12-24 VDC
typically this means there is a status light (12 or 24 VDC) for the connected door, connected to the relevant input (terminal
6, 7). When the status light is on, the green light also comes on in the app and the other light goes off, and vice versa.
16