Example:
-
Activate Temperature datalog
-
Temperature decimation factor = 1
-
Deactivate Humidity datalog
Frame structure from LSB to MSB:
Byte
Value
Info
0
0x55
Header for 1- message reconfiguration
1
0x28
ID Temperature datalog enable
2
0x01
Value to enable temperature datalog
3
0x29
ID Humidity datalog enable
4
0x00
Value to disable humidity datalog
5
0x2B
ID for temperature datalog decimation factor
6
0x01
Value for decimation factor = 1
5 Standard configuration
When the product is delivered, the standard configuration is the following:
Function
Status
Temperature Datalog
Activated with following parameters:
Period between measurements = 30min
Humidity Datalog
Activated with following parameters:
Period between measurements = 30min
Daily air quality
Deactivated
Temperature alert
Deactivated
Keepalive
Activated with following parameters:
Period: 24h