* USE ONLY THE SILICONE LUBRICANT SUPPLIED
1
Clean and lubricate* the insulating plug and the female interface of the coupling connector.
2
Insert the plug into the connector and tighten assembly: use a torque wrench with a 6-point socket of 22 mm and
tighten exerting
30
Nm (3 kgm or 22,1 foot-pounds) of torque.
In order to achieve the correct applied torque ensure that there is no lubricant on the threaded
parts.
1/2" - 12,7 mm
torque wrench
22 mm
6-point socket
22mm
30 Nm
basic
insulating
plug
coupling
connector
equipment
bushing
lubricate
INSTALLATION OF THE CAP
INSTALLATION OF INSULATING PLUG
protective
cap
protective
cap
Installation on insulating plug BIPR without
voltage detection point:
- Clean the inside of the cap and the outside surface of
the connector and insulating plug.
- Place the nylon vent rod along the insulating plug
(see fig.) to exhaust the air during assembly of
the cap.
- Push the cap
firmly
over the connector and onto the
insulating plug.
- Press the cap on all sides to make sure it is well
positioned over the connector. Position the cap with
the pulling tab pointing downwards.
- Remove the nylon vent rod.
Installation on insulating plug BIPA with voltage
detection point:
- Clean the inside of the cap and the outside surface of
the connector and insulating plug.
- Place the nylon vent rod along the insulating plug
(see fig.) to exhaust the air during assembly of the cap.
- Push the cap
firmly
over the connector and onto the
insulating plug.
-
Press the centre of the cap onto the locking
point until it snaps into place.
Press the cap on all
sides to make sure it is well positioned over the
connector. Position the cap with the pulling tab
pointing downwards.
- Remove the nylon vent rod.
nylon vent
rod
nylon vent
rod
locking point