NewMar Power System Manual
M-CMDRII 063022
Page 20 of 43
Model: COMMANDER II AND COMMANDER II+
Version 1.0
7.4.2
EM4x Main PCB Alarm Mappings
Alarms can be mapped to any of the voltage free output relays fitted to the EM4x. Output states of either
Normally Open or Normally Closed can be selected (NO and NC states are for the de-energized relay). A
jumper is fitted to nominate the required output state, ensure the jumper is placed in the correct configuration
for installation requirements.
If an alarm is programmed for the relay to be normally energized (such as a low voltage alarm where loss of
power will put the alarm into its “active” state), then be sure to connect the remote wiring appropriately.
Table 2
lists alarm assignment for the EM4x controller as matches the relay outputs shown in
Figure 18
.
Figure 18: EM4x Relay Outputs
Table 2: IO Board 1 Relay Alarm Assignments
Relay
Output
Relay Label
(In NewMar Config.)
Alarms Mapped to Relay/Output
(All multiple states “OR-ed”)
Relay 1 CPU Fail
Relay 2 Non-Critical Alarms
Orange LED
(
For reference only. Actual system alarm mapping may vary)
Relay Outputs 1
-