4
Newmar • 1580 Sunflower Ave, Suite 100, Costa Mesa, CA 92626
Phone: 714-751-0488 • E-mail: [email protected]
5.
S
YSTEM
O
VERVIEW
The system is intended to be a complete power system in a box, so no connections need to be made
internally.
All the AC, DC (Load and Battery) connections are made at the rear of the unit.
Alarm connections are accessible from the front by pulling the Energy Manager forward.
The system is designed to be extremely simple to install and set up.
Note:
This system is supplied with the AC and DC earths connected unless chassis DC isolation is specified when
ordering. The standard -48 VDC system output has the DC Common in the positive side of the circuit (+ve earth
system). On +24 VDC systems, the DC Common has the negative side of the circuit (-ve earth system) connected to
system chassis/earth. The earth link can be removed from the system to isolate earths
5.1.
Power System
Standard Features
The base unit is supplied with the following standard options:
•
AC Input: Three sets of single-phase input terminals: A-L1, B-L1, C-L1 & A-L2, B-L2, C-L2 plus Earth are provided
to allow several input wiring options.
•
DC Output: maximum power output of 6.0kW (+24V rated to 3.0kW @ 24V, 3.3kW @ 27V), producing a maximum
current output of 125A/-48V (125A/ +27V).
•
Up to 3 x 37-amp (-48V or +24V) C2R-2000 or C2RX-2048 rectifiers 41.7A max (may be packaged separately) or 3
x 18-amp (-48V) C2R-1000 rectifiers
•
EM4x energy manager system controller (fully integrated in the system)
•
Battery Low Voltage Disconnect 125A rating
•
2x 100A Battery Circuit Breaker.
•
8x 10A, 4x 20A, 4x 30A default Load Circuit Breakers, these may be specified as different values (from 2A to 30A)
at time of order.
Note:
Two 3 position terminal block links/jumpers are provided (in manual bag) to allow one two wire AC input.
5.2.
Physical Dimensions and Weights
Model
Centurion II
Depth (Total)
350mm
Width (Total)
483mm (19” mount)
Height
88.9mm (2U)
Weight without rectifiers
8.4kg
Weight with max. rectifiers
13.2kg
Table 1
Load
Battery
ON
OF
F
o
-
ON
OF
F
-
o
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
I
1
2
3
4
5
6
7
8
9
10
11
12
13
14
15
16
RM3048HE
3.0kW 48 V D C
NEWMAR
RM3048HE
3.0kW 48 V D C
NEWMAR
RM3048HE
3.0kW 48 V D C
NEWMAR
48.7 V
0.0 A
0 W
6.1 A
295 W
-6.1 A
-295 W
29.1
%
ETR :
Battery
Discharge
!