Table 2: IO Board 1 Relay Alarm Assignments
Relay
Output
Relay Label
(In NewMar Config.)
Alarms Mapped to Relay/Output
(All multiple states “OR-ed”)
Relay 1 CPU Fail
Relay 2 Non-Critical Alarms
Orange LED
Relay 3 Critical alarms
Red LED
Relay 4 Spare
Relay 5 Spare
Relay 6 Spare
Buzzer
Red LED
7.7.
EM4x Main PCB Digital Input Alarm Mappings
General purpose inputs allow the Commander II & II+ system to monitor any external
equipment that includes relay or auxiliary outputs. The GPIP inputs are activated by
connecting the system positive (common) to the input terminal (configuration setup in the
EM4x can allow activation by connecting to system live).
General purpose inputs can also be configured as analogue inputs for purposes such as
battery midpoint monitoring and voltage monitoring.
These inputs may be assigned to contribute to alarm states within the monitor. The state
mapping is defined in the configuration file. Alarm mapping should be completed using the
EM4x software. Please refer to the EM4x manual for detailed information.
The inputs are normally activated by connecting system positive (usually system common) to
the input.