25
15272 Newsboy Circle
Huntington Beach,
CA 92649
Phone: 714-751-0488
Fax: 714-372-7930
E-Mail: [email protected]
PoweringTheNetwork.com
6.3 Charger Mode Specifi cations
Appropriate battery type
AGM
Charging Current
2Amp / 4Amp / 6Amp / 8Amp / 10Amp adjustable
Max Charger Current Limitation
Charging Algorithm
3-Step
Charger Voltage Setting @25 °C
Battery Type
Boost CC, CV
Float
24/48V DC
24/48V DC
AGM
28.2/56.4V DC
27.0/ 54.0V DC
Battery Temperature Control
Charging voltage is compensated according to battery temperature
-2.5mV / -3.0mV / -3.5mV / -4.0mV per cell per °C compensated coeffi cient
adjustable
Charger on when battery temperature between -20 °C to 50 °C
6.4 General Specifi cation
Dimension (WxDxH): Inches/mm: 15.75” x 9.45” x 5.23” / 400 x 240 x 133
Net Weight: Lbs. / Kgs: 27.5 / 13
Operation Temperature Range: -40° C ~ 80° C for 120V AC model
Storage Temperature Range: -50° C ~ 80° C
Relative Humidity: 5% ~ 95% non-condensing
Audible Noise: < 53dB
Cooling: Forced Air
EMI: FCC Part 15, Subpart B, Class A
Safety: UL1778, CSA 107.3