59
TABLE 14A: BECKETT AFG BURNER SPECIFICATIONS
Beckett AFG
Boiler Model Firing Rate
GPH
Settings
Nozzle
3
Pump
Pressure
Head
(Setting)
Air
Shutter
Air
Band
GPH x Angle Type
2
Shipped
1
CL3-091
0.65
L1
8
0
0.55 x 70B (Delavan)
p
Loose
140
p
CL3-105
0.75
L1
6
0
0.65 x 45B (Hago)
Installed
140
CL3-140
1.00
L1
10
1
0.85 x 45B (Hago)
Installed
140
CL4-126
0.90
L1
7
0
0.75 x 45B (Delavan)
Installed
140
CL4-175
1.25
V1(0)
10
1
1.00 x 45B (Hago)
Loose
175
CL4-210
1.50
V1(3)
10
2
1.10 x 45B (Hago)
Installed
175
CL5-168
1.20
V1(3)
10
0
0.90 x 45B (Hago)
Installed
175
CL5-245
1.75
V1(3)
7
3
1.35 x 45B (Hago)
Installed
175
CL5-280
2.00
V1(4)
10
3
1.50 x 45B (Hago)
Installed
175
1
Beckett low firing rate baffle required on CL3-091 (0.65 GPH) application only; shipped loose with nozzle.
2
Nozzle(s) for alternate boiler model firing rate(s) are shipped loose in bag attached to the
burner designated by corresponding symbol, i.e. (
p
) = CL3-105.
3
Single stage fuel pump is standard, two stage fuel pump is optional. Burner manufacturer has preset
single stage fuel pump to settings shown in table above.
XI: BURNER SPECIFICATIONS
Summary of Contents for CL3-105
Page 46: ...46 Figure 31 Cleaning of Boiler Flueways VIII Boiler Cleaning continued ...
Page 52: ...52 X Repair Parts continued Bare Boiler Assembly Exploded View ...
Page 57: ...57 Beckett AFG Burner X Repair Parts continued ...
Page 63: ...63 SERVICE RECORD DATE SERVICE PERFORMED ...
Page 64: ...64 ...