5
Sleeping Mode
The device is on and in the
network
Sleeping period: Min Interval.
When the reportchange exceeds setting value or the state changes, a data report will be sent
according to Min Interval.
Low Voltage Warning
Low Voltage
Threshold
2.4V
5. Data Report
The device will immediately send a version packet report and a data report.
Data will be reported by default setting before any configuration.
Default setting:
Max Interval
= 0x0E10 (3600s)
Min Interval = 0x0E10 (3600s) (The voltage is detected every Min Interval by default.)
Battery Voltage Change: 0x01 (0.1V)
CO Trigger:
The CO concentration is sampled 30 seconds after the device is powered up, when the concentration is higher than 110 ppm,
the red indicator light flashes, the buzzer alarms and immediately sends a report (CO alarm bit is 1).
If the alarm continues, the report will be sent every 30 seconds. When the concentration drops below 110ppm, the flashing
end alarm will be stopped and an alarm will be sent to restore the report.
High Temperature Alarm:
After the device is successfully connected to the network, the temperature will be sampled once every 1 minute.
When the temperature is higher than 60°C, the buzzer will alarm, the red indicator will flash, and a report will be sent
immediately. (The fire alarm bit is 1.)
If the alarm continues, the report will be sent every 1 minute. When the temperature below 60°C, the flashing end alarm will
be stopped and an alarm will be sent to restore the report. (The fire alarm bit is 0.)
Note:
(1) The device report interval will be programmed based on the default firmware.
(2) The interval between two reports must be the minimum time.
The reported data is decoded by the Netvox LoRaWAN Application Command document and