7
5.2 Example of ConfigureCmd
FPort
:
0x07
Bytes
1
1
Var(Fix =9 Bytes)
CmdID
DeviceType
NetvoxPayLoadData
CmdID
– 1 byte
DeviceType
– 1 byte – Device Type of Device
NetvoxPayLoadData
– var bytes (Max=9bytes)
Description
Device
Cmd
ID
Device
Type
NetvoxPayLoadData
Off
R816B
0x90
0x73
Reserved
(9Bytes,Fixed 0x00)
On
0x91
Reserved
(9Bytes,Fixed 0x00)
Toggle
0x92
Reserved
(9Bytes,Fixed 0x00)
Clear
Energy
0x93
Reserved
(9Bytes,Fixed 0x00)
Read
CurrentStatus
0x94
Reserved
(9Bytes,Fixed 0x00)
Config
ReportReq
0x01
MinTime
(2bytes Unit:s)
MaxTime
(2bytes Unit:s)
CurrentChange
(2byte)
Unit:1mA
PowerChange
(2byte)
Unit:1W
Reserved
(1Byte)
Fixed 0x00)
Config
ReportRsp
0x81
Status
(0x00_success)
Reserved
(8Bytes,Fixed 0x00)
ReadConfig
ReportReq
0x02
Reserved
(9Bytes,Fixed 0x00)
ReadConfig
ReportRsp
0x82
MinTime
(2bytes Unit:s)
MaxTime
(2bytes Unit:s)
CurrentChange
(2byte)
Unit:1mA
PowerChange
(2byte)
Unit:1W
Reserved
(1Byte)
Fixed 0x00)
(1) Turn off the R816B switch button
Downlink: 9073000000000000000000
(2) Turn on the R816B switch button
Downlink: 9173000000000000000000