4
(
1
)
Command Configuration Setting:
(
2
)
MinTime = 1min
、
MaxTime = 1min
、
BatteryChange = 0.1v
、
TemperatureChange = 1
℃
Downlink
:
019C003C003C0100640000
Response
:
819C000000000000000000
(
Configuration success
)
819C010000000000000000
(
Configuration failure
)
(
3
)
Read Configuration Setting:
Downlink
:
029C000000000000000000
Response
:
829C003C003C0100640000
(
Current configuration setting
)
The data transmission cycle example
Example#1
based on MinTime = 1 Hour, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange=0.1V
MaxTime
MaxTime
S
leeping(MinTime)
S
leeping(MinTime)
Note: MaxTime=MinTime. Data will only be report according to MaxTime (MinTime) duration regardless BtteryVoltageChange value.
Example#2
based on MinTime = 15 Minutes, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange= 0.1V.
MaxTime
S
leeping(MinTime)
sleeping
sleeping
sleeping
0H
15
th
M
30
th
M
45
th
M
1H
2H
Example#3
based on MinTime = 15 Minutes, MaxTime= 1 Hour, Reportable Change i.e. BatteryVoltageChange= 0.1V.
MaxTime
sleeping
sleeping
...
0H
15
th
M
30
th
M
45
th
M
1H
1H 10
th
M
1H 25
th
M
1H 40
th
M
1H 55
th
M
2H 10
th
M
Wakes
up
and
collects data
3.6V
Does not report
Wakes
up
and
collects data
3.6V
Does not report
Wakes
up
and
collects data
3.6V
Does not report
Wakes up and
collects data
REPORTS
3.6V
Wakes
up
and
collects data
REPORT 3.6V
Wakes
up
and
collects
data
REPORTS
3.6V
Wakes up and collects data
3.5V |3.5-3.6|=0.1
REPORTS 3.5V
Wakes up and
collects data
3.5V Does not
report
Wakes up and
collects
data
3.5V Does not
report
Wakes up and
collects
data
3.5V Does not
report
Wakes up and collects data
3.5V Does not report
Wakes up and
collects data
3.5V Does not
report
Wakes up and
collects
data
REPORTS 3.5V
Wake up and collects data
REPORTS 3.6V
Wakes up and collects data
REPORTS 3.5V
Wakes up and collects data
REPORTS 3.6V
Wakes up and
collects data
3.6V Does not
report
Users push the button,
REPORTS 3.5V.
Recalculate MaxTime.