4.

 

Set up Instruction

 

On/Off 

 

Power on 

Insert batteries. (users may need a flat blade screwdriver to open) 

Turn on   

Press and hold the function key for 3 seconds till the green indicator flashes once.   

Turn off (Restore to factory setting) Press and hold the function key for 5 seconds till green indicator flashes for 20 times. 

Power off 

Remove Batteries.   

Note 

1.

 

Remove and insert the battery; the device is at off state by default. 

2.

 

On/off interval is suggested to be about 10 seconds to avoid the interference of capacitor 

inductance and other energy storage components. 

3. At 1

st

 -5

th

 second after power on, the device will be in engineering test mode.   

 

Network Joining 

 

Never joined the network 

Turn on the device to search the network to join. 

The green indicator stays on for 5 seconds: success 

The green indicator remains off: fail 

Had joined the network 

(not at factory setting) 

Turn on the device to search the previous network to join. 

The green indicator stays on for 5 seconds: success 

The green indicator remains off: fail 

 

Function Key 

 

Press and hold for 5 seconds 

Restore to factory setting / Turn off 

The green indicator flashes for 20 times: success 

The green indicator remains off: fail 

Press once   

The device is in the network: green indicator flashes once and sends a report 

The device is not in the network: green indicator remains off 

 

Sleeping Mode 

 

The device is on and in the network 

Sleeping period: Min Interval. 

When the reportchange exceeds setting value or the state changes: send a data report according to 

Min Interval.   

 

Low Voltage Warning

 

 

Low Voltage 

3.2V 

Summary of Contents for R718AB

Page 1: ...ology Co Ltd This document contains proprietary technical information which is the property of NETVOX Technology It shall be maintained in strict confidence and shall not be disclosed to other parties...

Page 2: ...eport 5 5 1 Example of ReportDataCmd 5 5 2 Example of ConfigureCmd 6 5 3 Example for MinTime MaxTime logic 7 6 Installation 9 7 Information about Battery Passivation 11 7 1 To determine whether a batt...

Page 3: ...reatly increases to expand the communication distance Widely used in long distance low data wireless communications For example automatic meter reading building automation equipment wireless security...

Page 4: ...oftware platform data can be read and alerts can be set via SMS text and email optional Applicable to third party platforms Actility ThingPark TTN MyDevices Cayenne Improved power management for longe...

Page 5: ...etwork Turn on the device to search the network to join The green indicator stays on for 5 seconds success The green indicator remains off fail Had joined the network not at factory setting Turn on th...

Page 6: ...nge Reportable Change Any number between 1 65535 Any number between 1 65535 Can not be 0 Report per Min Interval Report per Max Interval The device will immediately send a version packet report along...

Page 7: ...yte 000000 Reserved Example of Uplink 01130124FF391A9E000000 1st byte 01 Version 2nd byte 13 DeviceType 0x13 R718AB 3rd byte 01 ReportType 4th byte 24 Battery 24 HEX 36 DEC 36 0 1v 3 6v 5th 6th byte F...

Page 8: ...me Note MaxTime MinTime Data will only be report according to MaxTime MinTime duration regardless BatteryVoltageChange value Description Device Cmd ID Device Type NetvoxPayLoadData Config ReportReq R7...

Page 9: ...ecommend to set the MinTime Interval value too low If the MinTime Interval is too low the device wakes up frequently and the battery will be drained soon 4 Whenever the device sends a report no matter...

Page 10: ...nsmission of the device The figure shows the scene where the temperature and humidity sensor R718AB is applied in the refrigerator It can also be applied to the following scenarios Restaurant refriger...

Page 11: ...ut the lid back on and tighten the four screws Note Please do not disassemble the device unless it is required to replace the batteries Do not touch the waterproof gasket LED indicator light function...

Page 12: ...orage period is more than one month from the date of battery production all the batteries should be activated If encountering the situation of battery passivation users can activate the battery to eli...

Page 13: ...elt some plastic parts Do not store the device in places that are too cold Otherwise when the temperature rises to normal temperature moisture will form inside which will destroy the board Do not thro...