2.2.2 Environment Requirements
Item Requirement
Machine Hall Space
When installing a machine frame array in one machine hall, the
distance between 2 rows of machine frames should be 1.2~1.5m
and the distance against wall should be no less than 0.8m.
Machine Hall Floor
Electric Isolation, Dust Free
Volume resistivity of ground anti-static material:
1X10
7
~1X10
10
,
Grounding current limiting resistance: 1M
(Floor bearing should be greater than 450Kg/
㎡
)
Environment
Temperature
5~40
℃
(sustainable )
,
0~45
℃
(short time)
,
installing air-conditioning is recommended
Relative Humidity
20%~80% sustainable 10%~90% short time
Pressure 86~105KPa
Doors & Windows
Install rubber strip for sealing door-gaps and dual level glasses
for window
Walls
May be covered with wallpaper, or dark paint.
Fire Protection
Fire alarm system and extinguisher
Power
Requiring device power, air-conditioning power and lighting
power are independent to each other. Device power requires AC
power 220V 50Hz. Please carefully check before running.
2.2.3 Grounding Requirement
All function modules’ good grounding designs are the basis of reliability and stability of
electronic devices. It is the most important guarantee of surge protection and interference
rejection. Therefore, the system must be grounded.
Coaxial cable’s outer conductor and isolation layer should keep proper electric conducting
with the metal housing of device.
Grounding conductor must adopt copper conductor in order to reduce high frequency
impedance, and the grounding wire must be as thick and short as possible.
Make sure the 2 ends of grounding wire conduct electricity and are not rusty.
It is prohibited to use any other devices as a part of grounding electric circuit
The area of the conduction between grounding wire and device’s frame should be no less