PAGE 3
NEP04/03
www.hvacquick.com 877-711-4822
Control Equipment
PTC
description:
description:
description:
description:
description:
The ptc is a powerful microprocessor based menu driven temperature controller for heating and cooling
applications
. Please read the following information to maximize the potential of this powerful thermostat.The following
are some highlights of the
ptc
:
* p.i. analog heating and cooling outputs
* 2 sequential p.w.m. heating outputs to proportionally
drive solid state relays
* 2 fully programmable dry contact relays to be used in
heating and/or cooling applications
* high signal selections outputs from multiple ptc's to
be used by a master system
* individually programmable night set back/ set up
* night set back override
* intelligent self-optimizing morning self start
* minimum position setting for heating and cooling output
* programmable min and max allowable temperature setting
* selectable internal/external sensor
* led display
* programmable Celcius or Fahrenheit display
* plug in easily removable thermostat body
* attractive flat casing
button
button
button
button
button
functions:
functions:
functions:
functions:
functions:
The up button is used to increase
the temperature set point (warmer)
while the thermostat is operating in
user mode. The up button is also
used to increase a given parameter
when in program mode.
Similarly, the down button is used
to decrease the temperature
setpoint (cooler) or decrease a
parameter in program mode.
The menu button is used to place
the ptc into program mode, and to
advance the program function to
the next menu.
The enter button is used to store
the program function parameter into
memory. Once a value is stored in
memory, the ptc will remember that
value even if the power is turned off
at the thermostat for several years.
When a parameter is being stored,
the led display will flash in a
circular fashion. You will notice that
when changing the setpoint, the led
display will do a circular flash. This
is because a new setpoint is being
entered into the memory of the ptc.
In program mode if this flash does
not occur you have not stored that
parameter into memory! if you do
not wish to change the value in me-
mory of a parameter, simply do not
press the enter button and push
the menu button to go to the next
program level.
Night Set Back Indicator: When NSB
is ON, the NSB Indicator will light. If
you wish to locally override the NSB,
momentarily push either the UP or
DOWN button. NSB will be cancelled
for 2 hours and the NSB light will turn
off until the NSB is re-established.
hole for
mounting
screw
temperature
and function
led display
up
button
minimum
position
HEAT
minimum
position
COOL
night
set back
indicator
down
button
menu
button
enter
button
sensor
shunt
exterior / interior
modes