PTC

program level organization:  cont.

Push 

MENU

 again.  The fourth program level mes-

sage ( C b )  will be displayed for 2 se-
conds, fol         lowed by the setpoint of

contact B

.  The format is the same as described

above for 

contact A

, and adjustments to the setpoint

are made in the same way.

Contact A and Contact B are totally independent.
You may select two heating contacts, two cooling
contacts, or one heating and one cooling contact.
Their setpoints can be wherever you choose.

Push 

MENU

 again.  The fifth program level message

( S b )  will be displayed for 2 seconds,
followed by the 

night set back

deadband

.  This is the total deadband (over and

under the setpoint) applied when the night set back
terminal is connected to common.
Using the  

up

  or  

down

 button,  adjust the night set

back deadband to the value
required and press 

ENTER

 to

store that value in memory.

Push 

MENU

 again. The sixth program level message

 ( P b ) will be displayed for 2 se-conds,
followed by the 

proportional band

.

The 

ptc

  operates using a p.i. algorithm, with the

integral  terms optimized automatically by the ther-
mostat.  But  since the proportional band has the
greatest effect on the output, adjusting the propor-
tional band

4

will allow you to tailor the response of the ptc to any
given application.  For most V.A.V applications, the
usual proportional band is 2 to 3

0

C (3.5 to 5.5

0

F ). For

many applications where hot or chilled water coil is
used, a typical proportional band is 3 to 6 degrees 

0

C

(5.5 to 10.5

0

F).

Using the  

up

  or  

down

 buttons, adjust the propor-

                                    tional band to the value re-
                                   quired. Press the 

ENTER

button to store the value in memory.

Push 

MENU

 again.  The seventh program level mes-

sage ( r l c ) will be displayed followed by
the soft start ramp time.  Since the soft

start feature is only useful if modulating electric heating
is used, you may disable this feature.  To turn off the
soft start function, set the soft start ramp time to 00.  If
modulating electric heating is used, normally the soft
start ramp time is set the same as the morning warm
up period.

Push the  up  or down  buttons to set the soft start
                                  ramp time to the number of
                                  minutes required.

Push the 

ENTER

 button to store this value in memory.

3

5

6

7

Summary of Contents for PTC

Page 1: ...c n e p t r o n PAGE1 NEP04 03 www hvacquick com 877 711 4822 Control Equipment PTC modulating wall thermostat PTC PTC PTC PTC PTC...

Page 2: ...150 C 00 to 270 F deadband expansion 2 hours deadband expansion around setpoint Opti mized soft start for peak electrical demand reduction Warm up ramp time programmable over 0 to 99 minutes 0 to 75 i...

Page 3: ...ton is also used to increase a given parameter when in program mode Similarly the down button is used to decrease the temperature setpoint cooler or decrease a parameter in program mode The menu butto...

Page 4: ...may be used to actuate several triac switches or even a thermo electric valve directly 10 time proportional modulation output 2 1 or 24vdc output This output is similar to pin 9 except that the output...

Page 5: ...ool is required and the programming sequences are all menu driven Description of all programming steps is done in the order in which they appear while actually programming the thermostat Please look a...

Page 6: ...nd it uses default factory settings Setpoint change To check the setpoint momentarily press the UP or DOWN button The display will automati cally show the setpoint To change setpoint press the UP or D...

Page 7: ...mum setpoint you wish the user to have access to Once that is done push the ENTER button to store this value in memory Note that if you wish to fix the temperature setpoint to one value ie not adjusta...

Page 8: ...proportional band The ptc operates using a p i algorithm with the integral terms optimized automatically by the ther mostat But since the proportional band has the greatest effect on the output adjus...

Page 9: ...f for example the ptc was reading 2 degrees lower than the actual temperature set the temperature calibration adjustment to 2 Adjust the calibration value by pushing the up or down buttons When finish...

Page 10: ...designed to fit on standard 2020 electrical box thermostat box or directly on dry wall ensured to align pin guides with the base board for proper fitting to open grab top and bottom of front cover an...

Page 11: ...unit Terminal strip Fan on 24 hours L1 L2 R R Heater Notes use intermediate relay R for high current load over 1A discharge air temp control with remote temp indicator return air duct heater fresh air...

Page 12: ...711 4822 NEP04 03 national environmental products montreal canada Control Equipment PTC Two typical zone VAV box control Cooling ramps modulates VAV Box actuator heating ramps modulates terminal rehe...

Reviews: