Parameter
Description
CU-OH04 factory
setting
Factory setting
SCB-04B
CP143
Set point cooling activity zone 4
Can be set from 20 to 30°C
not available
25°C
CP144
Set point cooling activity zone 5
Can be set from 20 to 30°C
not available
25°C
CP145
Set point cooling activity zone 6
Can be set from 20 to 30°C
not available
25°C
CP200
Room temperature set point in forced mode
Can be set from 5 to 30°C
20°C
20°C
CP320
Circuit operating mode:
= timer programming
= manual mode
= frost protection mode
0
0
CP350
Do not modify this setting.
not available
55°C
CP360
Do not modify this setting.
not available
10°C
CP510
Circuit temporary room temperature set point
Can be set from 5 to 30°C
20°C
20°C
CP540
Temperature set point for SWIMMING POOL mode
Can be set from 0 to 39°C.
not available
20°C
CP550
Chimney zone
= off
= on
0
0
CP570
Do not modify this setting.
0
0
CP660
Select the icon to display this zone on the room sensor:
= none
= all
= bedroom
= living room
= office
= outside
= kitchen
= basement
3
3
Important
DP : Direct Hot Water Parameters = Domestic hot water tank
parameters
Tab.8
List of parameters in the
sub-menu of the User menu
Parameter
Description
CU-OH04 factory
setting
DP060
Number of timer programs selected for domestic hot water production mode
Can be set from 0 to 2
0
DP070
Domestic hot water temperature set point in comfort mode
Can be set from 40 to 65°C.
55°C
DP080
Domestic hot water temperature set point in reduced mode
Can be set from 10 to 60°C.
10°C
DP200
Domestic hot water production mode:
= timer programming
= manual mode
= frost protection mode
0
DP337
Water temperature set point in the domestic hot water tank in holiday mode
Can be set from 10 to 60°C.
10°C
8 Control panel settings IniControl 2
26
EFU-S
7719764 - v02 - 16112018