background image

16

 

 

      FG7B CONTROLLER        

 

    

   Firmware upgrade       

 

 

         

 

 
 
 
FIRMWARE UPGRADE 
 

1)

 

Load  on  a  USB  stick  the  latest  available  software  for  the  FG7B  control  unit.  The  file 
normally  is  called  nemtekfg7BDruid???  where  ???  normally  is  a  number  indicating  the 
version. 
The latest version will be available from Nemtek or its distributors. 

2)

 

If  you  can  access  the  USB  port  without  removing  the  unit  from  its  base  than  start  the 
unit otherwise remove the unit from  its base for access to the  USB port and then  start 
the unit. 

3)

 

Go to the PIN tab and select Installer, enter the Installer code and press enter. 
Make sure it stays on Installer and does not go back to Select. 

4)

 

Place the USB stick in the USB port on the control board. 

5)

 

Go to the System tab and check the version number and then press firmware upgrade 
(the screen will go black and says system login). 

6)

 

If jumper 4 and 6 are set to auto reset (normal operation), then after about two minutes 
the application will restart. Otherwise one can push the B3-PWR button and this will close 
the application and after the Nemtek logo has disappeared from the screen you press the 
B3-PWR button again to restart the unit. 

7)

 

Go back to the System tab and check that the new version has been loaded. 

8)

 

Remove the stick and place the unit back in its base. 

 
 

THE FG7 WEB INTERFACE 

 

The FG7 has a web interface which can be used for: 

1)

 

Viewing mapping files loaded in the FG7 

2)

 

Uploading new mapping files 

3)

 

Uploading new site images 

4)

 

Switching between LCD touchscreen and HDMI display 

5)

 

Up loading new program files 

 
To use the web interface you will need the IP address of the control unit in the FG7 which is 
displayed under the NET tab in the FG7 as well as the installer pass word and a computer set to 
the correct IP range for the IP address of the control unit.

 

 

FG7C CONTROLLER

                     

Document      

Connecting to the web interface 
 

1)

 

Open the FG7 and connect a network cable from the computer to the network connector 
on the control board inside the FG7. 

2)

 

Open the internet browser on the computer and enter on the address bar the IP address 
which is displayed under the NET tab of the FG7 (make sure the that the computers IP 
range is suitable for this IP address) 

3)

 

The FG7 configuration screen should now show on the computer 

 
 

Summary of Contents for FG7B

Page 1: ...INSTALLERS MANUAL Revision 1 6 6 June 2018 GROUP OF COMPANIES FG7B CONTROLLER for DRUID 25 28 NETWORKS ...

Page 2: ...NTROLLER Table of Contents INTRODUCTION 3 OPENING THE FG7B 3 HARDWARE 4 6 PROGRAMMING THE FG7B 7 11 MAPPING 12 15 FIRMWARE UPGRADE 16 FG7 WEB INTERFACE 17 THIRD PARTY INTEGRATION 18 DOCUMENT REVISION HISTORY 18 ...

Page 3: ...ed circuit boards and software to provide the required functionality Warning Test the functionality of the system after configuration and before commissioning OPENING THE FG7B On the opposite side to the LCD display are two screws that need to be removed With the LCD facing you slide the LCD gently to one side by approximately 15mm Leverage the LCD out as shown in the picture A green printed circu...

Page 4: ...is 12Vdc and is polarity protected The board also monitors and process the different communication signals before sending the information to the control unit You will find jumpers connecters and leds on the board for selecting connecting and indicating The control unit host the software and has all communication ports on board ...

Page 5: ...no auto reset of the control unit Watch Dog timer 2 JP4 1 Down for auto reset of the power supply with transmission failure of the control unit Up for no auto reset of the power supply CONNECTORS The connectors on the IOT1601JM board are self explanatory However if communication will be made through a NemLink card then the connector J7 should be used with the comms cable supplied with the unit jum...

Page 6: ...g software uploading site images downloading logs and can also be used for a mouse so that a pointer can be used on the touch screen display HDMI PORT The HDMI port is a standard micro HDMI connector To activate the HDMI port a shell script has to be loaded contact distributor for details and the touchscreen ribbon cable has to be disconnected from connector LCD1 brown ribbon cable A USB mouse sho...

Page 7: ...ise one can push the B3 PWR button and this will close the application and after the Nemtek logo has disappeared from the screen you press the B3 PWR button again to restart the unit 4 Check under the system tab that the number of energizers is now correct CONFIGURE THE NUMBER OF IO CARDS ON THE NETWORK 1 On the FG7 press the PIN tab on the top screen and select Installer enter the appropriate PIN...

Page 8: ...the addresses utilised on the system the faster the system response Because an energizer only updates its own parameters once a second there is little point in updating the FG7 display faster than that A combination of twenty addresses on a FG7 network bus gives the optimal performance in terms of speed versus hardware utilization The number of IO Cards used on the system can vary from zero to a m...

Page 9: ...then show a tick indicating that the setting is selected The following settings can be selected Audible alarm Alarm Sensor mode Show sync loss Nemlink Proxy AbsoluteIO Failsafe Off LV AUDIBLE ALARM The buzzer inside the FG7 is enabled when the Audible Alarm tick box is ticked The buzzer will sound when there is an alarm or service condition If unticked the buzzer is disabled ALARM SENSOR MODE If t...

Page 10: ...luteIO on the system tab FAILSAFE When third party software or Nemtek FenceProbe is used and the connection between the application and the FG7 is lost then the FG7 will automatically reset to enable the application to reconnect If Failsafe is not ticked than after the reset the energizer will come On in High Voltage mode by ticking Failsafe and selecting Off and or LV the energizers will after re...

Page 11: ...nfirm your entry 7 You can randomly do all energizers zones and gates using steps 3 to 6 above 8 When you are happy with the zone and gate lines press Save 9 The system will automatically load this graphic layout on power up You may after entering Installer mode edit any sector independently and then re save 10 The labels E1 Z1 Energizer Address Zone number and E1 Z2 etc are placed automatically a...

Page 12: ... any alarm condition note 1 that will activate relay 1 2 Only Fence 1 Alarm activates relay 1 3 The combination of any alarm condition note 1 that will activate relay 2 6 Fence 1 or Fence 2 alarm activates relay 2 2 4 4 The combination of any alarm condition note 1 that will activate relay 3 14 Fence 1 or Fence 2 or Gate Alarm activates relay3 2 4 8 5 The combination of any alarm condition note 1 ...

Page 13: ... relays If the one with 5 relays is used then line 7 8 and 9 can be made 0 Table 2 How the numbers are associated with each alarm state Energizer State Number COMMS FAIL 1 FENCE 1 ALARM 2 FENCE 2 ALARM 4 GATE ALARM 8 SERVICE ALARM 16 TAMPER ALARM 32 SYNC FAILURE 64 ZONE 1 ON 128 ZONE 1 HIGH VOLTAGE 256 ZONE 2 ON 512 ZONE 2 HIGH VOLTAGE 1024 MAINS PRESENT 2048 PANIC ALARM 4096 Multiple energizers a...

Page 14: ...nergizer in HV LV mode 16 32 128 4 Inputs that are valid on this IO card note 4 51 Inputs 1 2 5 and 6 are used 1 2 16 32 5 The Energizer Address that IO card 34 will communicate with unless global 2 Energizer 2 6 The above sequence repeated etc etc Notes 4 Table 4 has a number associated with each IO card input 5 Select the appropriate numbers and add them for the inputs to be recognized If the nu...

Page 15: ... the FG7 web interface Requirements Flash drive loaded with nemshell7BText1 sh and with folder NemText Inside folder NemText place etoimapplus txt and or itoemap txt these two files should be made in Notepad Procedure 1 Connect power to the FG7 unit 2 Place the flash drive in the USB connector of the FG7 unit make sure there is only one nemshell on the flash drive 3 On the top of the screen go to ...

Page 16: ...tion and after the Nemtek logo has disappeared from the screen you press the B3 PWR button again to restart the unit 7 Go back to the System tab and check that the new version has been loaded 8 Remove the stick and place the unit back in its base THE FG7 WEB INTERFACE The FG7 has a web interface which can be used for 1 Viewing mapping files loaded in the FG7 2 Uploading new mapping files 3 Uploadi...

Page 17: ...ct all files You can only load guf5e files for firmware updates image13r370 png files for site images and the mapping files itoemap txt or etoimapplus txt 3 Once the file is selected you have two options Press Get File and re enter the installer password and the selected file will be down loaded into the FG7 or Click on View File Only and press Get File In this case the file chosen will be display...

Page 18: ... will remain identical to the mapping in the third party software the system would not change due to the communication break If the AbsoluteIO option has been ticked under the system tab the third party software would still have control but if the communication to the FG7 fails then control would be given to the mapping of the inputs of the IO card s and not to the FG7 User see AbsoluteIO DOCUMENT...

Page 19: ...19 End of document ...

Reviews: