CHAPTER 1 GENERAL INFORMATION
1.1 USER’S MANUAL CONTENT
1.2 INTRODUCTION
1.2.1 General description
1.2.2 Configurations
1.2.4 Output connections
1.2.5 Analog voltage programming
1.2.6 Parallel operation
1.2.3 Control via the serial communication port
This user’s manual contains the operating instructions, installation instructions and specifications of
the ZUP series. For information related to operation with GPIB control, refer to Nemic-Lambda GP485
user’s manual.
The ZUP series are wide range output switching power supplies with laboratory performance. The ZUP
series is power factor corrected and operates from worldwide AC voltage range continuously. Output
voltage and current are continuously displayed and LED indicators show the complete operating status
of the power supply. The front panel controls allow the user to set the output parameters, the protection
levels (over-voltage / under-voltage)and arm the foldback protection to disable the output if the unit
switches from Constant-voltage mode to Constant-current mode.
The ZUP can be configured into a programmable power system of up to 31 DC outputs using the built-in
RS232 or RS485 communication port in the power supply. In a GPIB system the GP485 controller can
control up to 31 ZUP units in a single GPIB address.
Output connections are made to rear panel bus-bars. Either the positive or negative terminal may be
grounded or the output may be floated. The maximum potential (including the output voltage) that
either output terminal is from ground must not exceed 60V. Local or remote sense may be used. In
remote sense, the maximum voltage drop on each wire is 0.5V.
Analog inputs are provided at the rear panel for analog voltage programming of output voltage and
current, and On/Off control. Inputs are provided for resistive programming of the output voltage and
current.
ZUP units of the same output voltage and current rating can be paralleled in master-slave configuration
with automatic current sharing for power-up purposes.
The following parameters can be programmed via the serial communication port:
1. Output voltage setting
2. Output current setting
3. Output On/Off
4. Arming or release of the foldback protection
5. Over-voltage protection setting
6. ‘Soft’ under-voltage limit
7. Output voltage measurement
8. Output current measurement
9. Power supply start-up mode
(last setting or safe mode)
10. Over-voltage protection setting read
11.Under-voltage limit read
12. Remote/Local Control
5