Replace the belt guard after adjustment.

Check the temperature control valve TAV 50 MV. The
unit should be running when this is done. The best way
of doing this is to heat the thermal switch (TS) with a
hot air pistol, figure 9, so that it reaches a temperature
of about 80 °C (176 °F), when it closes. A simpler check
is to bridge the contacts with a screwdriver, figure 10.
The valve should open in either case and release coo-
ling air to the fan. A distinct change in sound shows the
valve is working.

Check the start-up valve SUV 200. The spring should
hold it closed when the unit is not running as well as
when the motor is starting in the Y-mode. It should
open (the spring comes under tension) when the motor
switches to D-mode. The valve needs 

compressed

air to work.

Check the bearing temperature, figure 11. Both bear-
ings are in the cage near the manual reset thermal
switches. Normal temperature range is 50-90 °C (122-
194 °F). If the temperature rises above 95 °C (203 °F)
or if one of the thermal switches has tripped (tempera-
ture > 110 °C (>230 °F)) the reason for this must be
established. Possible reasons are:

high ambient temperature or obstructed grids for 

cooling air and ventilation.

belt loose and slipping.

belt too tight, increasing the load on the transmission

bearing.

bearings worn or damaged. They should be replaced,

see below.

After some 15,000 hours of operation, or sooner if
there is reason to suspect damaged bearings, these
should be changed. This can be done in three ways. The
mounting instruction MI12-002, gives fuller details of
these alternatives, the tools needed and how to per-
form the task.

Spare parts and additional documentation

Spare parts list MX12-001 for VAC 20 is 

enc-

losed. VAC 2500 (30kW) corresponds to C-PAK 20-
1500 C. VAC 3000 (37kW) corresponds to C-PAK 20-
2500Ci.

Manual 

144211

 and spare parts list MX62-001 for

the temperature control valve TAV 50 MV are enclo-
sed if this valve is installed. (Should the option ASC be
installed its manual 

144342

 replaces the above

documents.)

Manual MA20-004 for the FlexFilter dust collector is
always enclosed. Should the FlexFilter be fitted with
type RF filter cleaning, then the AFC-RF manual 

144366

 is enclosed.

Manual 

144364

 for the High Vacuum Starter is

always enclosed.

Manual 

144365

 for flow restrictor FR 160 is enclo-

sed if FR 160 is installed..

Too high a temperature for a long period may dama-
ge the unit. While pumping may not be directly har-
mful the jerkiness and irregularity of the pumping
sound can be  disturbing. Standard VAC 20 units
are fitted with a thermal switch (TS) linked to a 
temperature control valve, TAV 50 MV, which opens
to permit an influx of cooling air if the temperature at
the fan reaches 79 °C (174 °F). The valve closes
when the temperature sinks to 60 °C (140 °F). At high
ambient temperatures the valve can remain open for
long periods.

The valve needs a supply of compressed air in
order to function. The parts list for TAV 50 is inclu-
ded with units so equipped.

An optional device against pumping is an Anti Surge
Control (ASC). This both adjusts temperature
(replacing TAV 50 MV) and prevents pumping.
The spare part list is supplied with all units fitted
with ASC.

On the bearing cage, close to the respective bear-
ings, are two manual reset thermal switches, RTS.
The circuit trips at about 110 °C (230 °F) and the
unit stops. An error indication is shown on the
starting equipment. The switches can be reset
when the temperature has fallen. The motor starter
must on no account allow a re-start before a safety
hold circuit has been reset.

As an option, a pressure-controlled switch (CAS) is
available, wired in series with the thermal switches
on the bearing cage. If the compressed air supply is
broken the circuit trips and the unit stops. An error
indication is shown on the starting equipment.

Maintenance

Read the section under Safety before carrying out
maintenance.

The following section is found in the manual for the
VAC 20. Maintenance of dust collectors with filters is
described in the manual for the dust collector.

An hour service meter is standard mounted in the
starter. The following service should be carried out
at intervals of 400-500 hours.

Check the tension of the belt transmission and
adjust if required. Replace worn or damaged belts.
New belts are liable to stretch slightly within the first
50-100 hours of use and should be more tightly ten-
sioned than used belts. The following figures can
serve as a guide for all VAC 20 models and give the
force F necessary to apply to one of the belts as
shown in figure 8 for 10 mm slack.
F = 24 N (5.4 lbf) for new belts. 
F = 20 N (4.5 lbf) for used belts.

Summary of Contents for C-PAK 20-1500 C

Page 1: ...High Vacuum Systems 144201 00 2009 12 18 C PAK 20 1500 C 30 kW 20 2500 Ci 37kW Manual Bedienungsanleitung Manuel Manuale Handleiding Instruktion Instruksjon K ytt ohje...

Page 2: ...2 4 3 5 1 4 8 6 2 9 7 1 2...

Page 3: ...3 4 3 5 10 14 11 13 12 4 15 17 16 18 19 21 22 23 20...

Page 4: ...9 6 4 4 8 7 11 SUV D 24VDC 30 31 10 24VDC 32 33 34 35...

Page 5: ...nualer f r de standardkompo nenter som ing r i C PAK 1 3 SE C PAK r alltid utrustad med en sk start up ventil SUV 200 som g r det m jligt att Y D starta C PAK ven om flera sugslangar r anslutna under...

Page 6: ...vs On digt luftfl de kar aggregatets energif rbrukning F rsta start Motorns rotationsriktning kontrolleras efter varje ny elektrisk inkoppling Fel riktning medf r d ligt sug och risk f r verhettning a...

Page 7: ...et efter justeringen Kontrollera temperaturregleringsventilen TAV 50 MV Aggregatet skall vara i drift vid kontrollen B sta kon trollen r att v rma termobrytaren TS med en varm luftpistol figur 9 s att...

Page 8: ...n C PAK building sites Once you have connected the power cable compressed air and suction hoses C PAK is ready to use C PAK is always equipped with a so called start up valve SUV 200 which makes it po...

Page 9: ...es that are not used must be disconnected so that the full capacity is available where it is best needed Unnecessary airflow increases the unit s energy consumption Initial start up Check the motor s...

Page 10: ...High Vacuum Starter is always enclosed Manual 144365 for flow restrictor FR 160 is enclo sed if FR 160 is installed Too high a temperature for a long period may dama ge the unit While pumping may not...

Page 11: ...erlagen f r die Standardkomponenten die zum C PAK geh ren vorher sorgf ltig durchlesen Startventil SUV 200 ausger stet mit dem das C PAK Y D gestartet werden kann selbst wenn mehrere Absaugschl uche w...

Page 12: ...bzutrennen damit die Gesamtkapazit t dort zur Verf gung steht wo sie am meisten gebraucht wird Unn tiger Luftstrom erh ht den Energieverbrauch des Aggregats Erststart Drehrichtung des Motors nach jede...

Page 13: ...er der Riemen gem Abbildung 8 mit einer Abfederung von 10 mm anzubringen ist F 24 f r neue Riemen F 20 f r benutzte Riemen Riemenschutz nach dem Einstellen wieder anbringen Temperaturreglerventil TAV...

Page 14: ...enimiento y pruebas en la unidad Lea los manuales incluidos en la entrega para m s informaci n sobre los componentes est ndar que se incluyen en la unidad C PAK El C PAK siempre viene equipado con una...

Page 15: ...conectar siempre un conducto de aspiraci n como m nimo Las tomas de aspiraci n que no se utili cen debe cerrarse con la correspondiente tapa de esta forma se canalizar el m ximo de caudal a la zona q...

Page 16: ...ercer sobre una de las correas seg n la figura 10 para obtener una curvatura de 10 mm F 24 N para correas nuevas F 20 N para correas usadas Terminado el ajuste monte nuevamente la protecci n Controle...

Page 17: ...leurs accessoires sont conformes avec les Directives 2006 95 EC 2006 42 EC Normes EN ISO 12100 1 EN ISO 12100 2 60204 1 Le chef de produits Romani Nous est responsable de la documentation technique D...

Page 18: ...Romani Nous term kmenedzser Atbilst bas deklar cija M s AB Ph Nederman Co pazi ojam un esam atbild gi par to ka Nederman iztr d jums C PAK 20 1500 20 2500 ar papildapr kojumu uz ko attiecas deklar ci...

Reviews: