3

1.4 Select country

Select the country in which the system will be installed.

Country-specific grid validation settings will be programmed 

automatically, such as:

Anti-Islanding - Frequency - Voltage - AC values

1.5 Select display text & language

Configure the status parameters to be shown on the four lines 

of the system display and the language of the display. Values 

shown are the actual system display settings. Select the status 

parameter to be shown on each line of the display via the drop-

down menu.

1.6 Select battery

Select and configure the connected battery. Select “not 

configured” if you are installing a system without batteries 

connected at the moment. When you install a battery, enter 

capacity/max DOD (depth of discharge) and DOD self-use.

Capacity (C10)

Enter the capacity in Ah/C10. When no C10 rating (capacity value 

of the battery discharged in 10 hours) is available, use the rating 

which is closest to C10. The capacity can be found on the battery 

itself or on the battery specification sheet.

Maximum depth of discharge (DOD) - backup

Enter the maximum depth of discharge allowed during a grid 

failure. This defines the percentage of the battery capacity that 

is used for backup purposes. For backup it is common to use as 

much of the available battery capacity as possible, to increase the 

available backup time. Deeply discharging a battery on a frequent 

basis reduces its service life considerably. So if the installation 

location is subject to frequent grid failures it is suggested that you 

configure a lower maximum depth of discharge to increase the 

battery service life (default is 100%).

Max depth of discharge (DOD) - self-use

Select the percentage of daily discharge of the battery to increase 

self-consumption of your generated energy. The battery will be 

discharged to this percentage on a daily basis. For lead-acid 

batteries a maximum depth of discharge of 50% is advised. A 

lower percentage will increase the service life of the batteries.

Figure 5: Country settting

Continue

Back

Figure 6: Parameters display

Continue

Back

Figure 7: Battery selection

Continue

Back

Continue

Back

Summary of Contents for PowerRouter

Page 1: ...u may download the installation tool from the website www PowerRouter com you will need your login details for this website The software installation tool can be used to configure PowerRouters with fi...

Page 2: ...gure a new system using the installation wizard The wizard automatically detects whether you are connected to a new PowerRouter system The wizard guides you through the minimal required settings to ge...

Page 3: ...the battery itself or on the battery specification sheet Maximum depth of discharge DOD backup Enter the maximum depth of discharge allowed during a grid failure This defines the percentage of the bat...

Page 4: ...output power of the grid module 5 latest grid disconnection events Solar Module status shows the status of the system s internal solar module Voltage and current of each solar string at this moment Lo...

Page 5: ...guring the system display Backlight When auto mode is selected the display will switch off after it has not been used for two minutes When always on is selected the display will never switch off Displ...

Page 6: ...ser selectable relay please configure relay 1 or 2 via a separate configuration option The following system conditions are available None Alarm is not used default Grid voltage Set trip level to activ...

Page 7: ...e deactivated Activation delay delay time in seconds before the alarm will be activated between 0 and 100 seconds Deactivation delay delay time in seconds before the alarm will be deactivated between...

Page 8: ...e how much power is connected as additional load to be switched on in watts Activate on load support activates if the percentage of the defined power of the load is available as an energy surplus Deac...

Page 9: ...relay Set relay signal type Normal default user selectable relay is activated when switched on Pulse activates the user selectable relay for a defined duration of between 1 and 10 seconds when switche...

Page 10: ...ed the system complies with the EEG2012 regulations in Germany by limiting its grid output power to 70 of nominal power by default The limitation can be optimized by entering the installed solar power...

Page 11: ...tery specification sheet capacity value of the battery discharged in 10 hours Maximum depth of discharge DOD Enter the maximum depth of discharge allowed during a grid failure This defines the percent...

Page 12: ...ctly Incorrect settings can damage the batteries At fixed float the batteries are charged with a constant voltage This can be used in a backup application where batteries may be charged over a long pe...

Page 13: ...consumption percentage since at lower discharge powers more energy can be extracted from the battery If the maximum discharge power is set too low not all the available battery energy is used In an id...

Page 14: ...take up to 15 minutes depending on which modules will be updated During this period the system will not be operational The installation tool already includes the latest firmware versions so no intern...

Page 15: ...loc Solar power www hoppecke com Battery type Number of batteries Battery pack size C10 Ah Maximum charge current Bulk voltage Float voltage 6V 4 OPzV 250 4x 205 Ah 41 A 28 8 V 27 0 V 6V 5 OPzV 300 4x...

Reviews: