background image

6 of 12

ISSUED: 02-21-13   SHEET #: 145-9017-1

E

F

G

SOLID CONCRETE 

CINDER BLOCK

Installation to Solid Concrete or Cinder Block

•  When installing wall mounts on cinder block, verify that you have a minimum of 1-3/8" (35 mm) of actual concrete 

thickness in the hole to be used for the concrete anchors. Do not drill into mortar joints! Be sure to mount in a solid 
part of the block, generally 1" (25 mm) minimum from the side of the block. Cinder block must meet ASTM C-90 
specifi cations. It is suggested that a standard electric drill on slow setting is used to drill the hole instead of a ham-
mer drill to avoid breaking out the back of the hole when entering a void or cavity.

•  Concrete must be 2000 psi density minimum. Lighter density concrete may not hold concrete anchor.

•  Make sure that the wall will safely support four times the combined load of the equipment and all attached hardware 

and components.

WARNING

1

CUT

A

W

A

Y

 VIEW

INCORRECT

CORRECT

wall 

plate

wall 

plate

plaster/
dry wall

plaster/
dry wall

concrete

concrete

1

3

2

F

Drill holes and insert anchors (

F

).

Place plate (

A

) over anchors (

E

) and secure with screws (

F

).

Tighten all fasteners.

  A

F

  E

concrete 
surface

NOTE:

 Make sure that there is a minimum of 16" 

horizontal distance between #14 x 2.5" screws (

E

). 

Make sure that pull-out mount assembly (

A

) is level, 

use it as a template to mark four mounting holes. Drill 
four 5/16" (8 mm) dia. holes to a minimum depth of 
2.5" (64 mm). Insert anchors (

F

) in holes fl ush with 

wall as shown (right). Place pull-out mount assembly 
(

A

) over anchors and secure with four #14 x 2.5" 

screws (

E

), and fender washers (

G

). Level, then 

tighten all fasteners.

•  Tighten screws so that wall plate is fi rmly attached, 

but do not overtighten. Overtightening can damage 
screws, greatly reducing their holding power.

•  Never tighten in excess of 80 in. • lb (9 N.M.).

•  Always attach concrete expansion anchors directly 

to load-bearing concrete.

•  Never attach concrete expansion anchors to 

concrete covered with plaster, drywall, or other 
fi nishing material. If mounting to concrete surfaces 
covered with a fi nishing surface is unavoidable, 
(not evaluated by UL) the fi nishing surface must be 
counter bored as shown below. Be sure concrete 
anchors do not pull away from concrete when 
tightening screws. If plaster/drywall is thicker than 
5/8" (16 mm), custom fasteners must be supplied 
by installer (not evaluated by UL).

WARNING

A

Summary of Contents for Video Wall Mount PD02VW MFS 46 55 L

Page 1: ... 13 SHEET 145 9017 1 Max UL Load Capacity 125 lb 57 kg Installation and Assembly Full Service Video Wall Mount Model PD02VW MFS 46 55 L Designed for NEC MultiSync 46 and 55 XUN V XS and P Series Manufactured by Peerless AV ...

Page 2: ...with basic building construction and fully understands these instructions Make sure that the supporting surface will safely support the combined load of the equipment and all attached hardware and components Never exceed the Maximum UL Load Capacity See page one If mounting to wood wall studs make sure that mounting screws are anchored into the center of the studs Use of an edge to edge stud finde...

Page 3: ... mesh sleeve not shown 1 600Ͳ1014 D M5 x 10 mm socket pin typeͲF screw 2 520Ͳ1164 E 14 x 2 5 hex head wood screw 4 5S1Ͳ015ͲC03 F concrete anchor 4 590Ͳ0320 G fender washer 4 540Ͳ1008 H nylon shoulder washer 4 590Ͳ2233 I M6 x 12 mm socket pin screw 4 520Ͳ1050 J M8 x 15 mm socket pin screw 4 520Ͳ1068 K 4 mm allen wrench 1 560Ͳ9646 L cable tie not shown 2 560Ͳ9711 ...

Page 4: ...ine horizontal spacing To determine edge of second mount add Z to edge or first mount Vertical Spacing Location Horizontal Spacing Location Vertical Location X 10 00 750 OR 1 580 Y1 OR Y2 DISPLAY WIDTH 35 Z SPACING BETWEEN MOUNTS Horizontal Location DISPLAY WIDTH DISPLAY HEIGHT X Y2 Y1 750 1 580 10 00 16 00 20 00 24 00 17 50 Z To determine lower mounting slot position of second mount add display h...

Page 5: ...assembly A is level secure it using four 14 x 2 5 wood screws E and fender washers G as shown below Installer must verify that the supporting surface will safely support the combined load of the equipment and all attached hardware and components Tighten wood screws so that wall plate is firmly attached but do not overtighten Overtightening can damage the screws greatly reducing their holding power...

Page 6: ...anchors E and secure with screws F Tighten all fasteners A F E concrete surface NOTE Make sure that there is a minimum of 16 horizontal distance between 14 x 2 5 screws E Make sure that pull out mount assembly A is level use it as a template to mark four mounting holes Drill four 5 16 8 mm dia holes to a minimum depth of 2 5 64 mm Insert anchors F in holes flush with wall as shown right Place pull...

Page 7: ...security screws using 4mm allen wrench K to lock in place Attaching Adapter Brackets to Pull Out Mount Assembly DETAIL 1 NOTE Make sure to use largest hole pattern on back of display Attach adapter brackets B to back of display using four M6 x 12 mm socket pin screws I with nylon shoulder washer H or four M8 x 15 mm socket pin screws J as shown below B H I or J 2 400 mm 300 mm 200 mm PLP MAX VESA ...

Page 8: ... below to determine position of display NOTE Each knob can be adjusted independently for fine tuning adjustments 4 Turn knob CLOCKWISE to raise side Turn knob COUNTER CLOCKWISE to lower side UP ROTATE LEFT ROTATE RIGHT Pull Out Mount Assembly Adjustment ...

Page 9: ...y NOTE Each knob can be adjusted independently for fine tuning adjustments 5 Turn knob CLOCKWISE to move corner toward the wall Turn knob COUNTER CLOCKWISE to move corner away from the wall IN OUT TILT BACKWARD TILT RIGHT TILT FORWARD Adapter Bracket Adjustment BACK BACK BACK BACK BACK BACK ...

Page 10: ...losed during normal use and operation Open and Close Pull Out Mount Assembly A A Display cables can be routed through top or bottom of pull out mount assembly A NOTE Use mesh sleeve M and cable ties L for cable management NOTE Cable ties and cable management slots on pull out mount assembly A can be used to secure display cables Cable Management DETAIL 3 CABLE MANAGEMENT SLOTS LOCKING TAB LOCKING ...

Page 11: ...on Open Adapter Brackets B B B B DISPLAY NOT SHOWN FOR CLARITY KICK STAND BACK RELEASE STRAP Close Adapter Brackets Slightly pull display away from wall to release kick stand while pulling down on back release straps on adapter brackets B as shown below Support the display until the adapter brackets B are engaged in the closed position NOTE Once back release strap is pulled adapter brackets B kick...

Page 12: ...12 of 12 ISSUED 02 21 13 SHEET 145 9017 1 9 To prevent locking tabs from releasing secure using two M5 x 10 mm socket pin type F screws D Pull Out Mount Assembly Optional Security D LOCKING TAB ...

Reviews: