background image

 

Preface

vii

Preface

Purpose of This Manual

The 

Express5800/320

Fc

: Site Planning Guide

 documents the site requirements and 

customer responsibilities related to preparing a site for the installation of 
Express5800/320

Fc

 systems.

Audience

This manual is intended for those responsible for preparing a site for the installation of 
an Express5800/320

Fc

 system.

Notation Conventions

This document uses the notation conventions described in this section.

Warnings, Cautions, and Notes

Warnings, cautions, and notes provide special information and have the following 
meanings: 

W A R N I N G

!

A warning indicates a situation where failure to take 
or avoid a specified action could cause bodily harm or 
loss of life. 

C A U T I O N

!

A caution indicates a situation where failure to take or 
avoid a specified action could damage a hardware device, 
program, system, or data. 

N O T E

A note provides important information about the operation 
of an Express5800/320

Fc

 system.

Summary of Contents for Active Upgrade Express5800/320Fc

Page 1: ...NEC Corporation of America 456 01723 000 Express5800 320Fc Site Planning Guide ...

Page 2: ... Software described in NEC a is the property of NEC and or its licensees b is furnished only under license and c may be copied or used only as expressly permitted under the terms of the license NEC documentation describes all supported features of the user interfaces and the application programming interfaces API developed by NEC and or its licensees Any undocumented features of these interfaces a...

Page 3: ...nts 2 1 Cabinet Requirements 2 1 Monitor Requirements 2 4 3 Space Planning 3 1 Room Requirements 3 1 Planning for Cables 3 2 4 Electrical AC Power Planning 4 1 Redundant Power Sources 4 1 AC Power Service Requirements 4 2 Power Outlet Requirements 4 4 Connecting a System Directly to Two Separate Power Sources 4 5 NEC Supplied Power Cords 4 6 System Power Cords 4 7 PDU Power Cords 4 8 Power Cords f...

Page 4: ...phone Line Planning 6 1 Network Cable Requirements 6 1 Telephone Line Requirements 6 2 Site Planning for Systems in an ftGateway Group 6 3 Appendix A System Specifications A 1 System Specifications A 1 Appendix B Electrical Circuit and Wiring Information B 1 Fault Protection Requirements B 1 Grounding Considerations B 1 Circuit Wiring Diagrams B 3 Electrical Power Connectors B 9 Appendix C Standar...

Page 5: ... e l p m a x E d n u o r G r a t S 1 B e r u g i F 3 B g n i l e b a L t u p n I r e w o P 2 B e r u g i F Figure B 3 Single Phase 120 Volts AC Circuit Connection B 4 Figure B 4 Single Phase 240 Volts AC Circuit Connection B 5 Figure B 5 Split Phase 120 240 Volts AC Circuit Connection B 6 Figure B 6 Three Phase 208 Volts AC Y or Source Circuit 7 B l a r t u e N o t e s a h P n o i t c e n n o C Fi...

Page 6: ... A Side External Power Outlet Requirements No PDUs 4 5 Table 4 8 Worksheet B Side External Power Outlet Requirements No PDUs 4 5 Table 4 9 System Power Cords to AC Power 4 7 Table 4 10 Systems Power Cords to a UPS 4 7 Table 4 11 PDU Power Cords to AC Power 4 9 Table 4 12 System Power Jumper Cables to a PDU 4 9 Table 4 13 Power Cords for Optional Components 4 9 Table 5 1 APC Symmetra Models for PDU...

Page 7: ...ons This document uses the notation conventions described in this section Warnings Cautions and Notes Warnings cautions and notes provide special information and have the following meanings W A R N I N G A warning indicates a situation where failure to take or avoid a specified action could cause bodily harm or loss of life C A U T I O N A caution indicates a situation where failure to take or avo...

Page 8: ... successfully Getting Help If you have a technical question about Express5800 320Fc hardware or software try these online resources first Online support from NEC Technical Support You can find the latest technical information about an Express5800 320Fc through online product support at the NEC Technical Support Web site http support necam com servers ft Online product support for Microsoft product...

Page 9: ...latory notices are provided in Appendix C Standards Compliance of this site planning guide Although this guide documents modem functionality modems are not available for all systems Ask your sales representative about modem availability ...

Page 10: ...Preface x Express5800 320Fc Site Planning Guide ...

Page 11: ...for the system or cabinet and for a desk or table to accommodate components outside a cabinet Also provide enough space for servicing the systems and components Purchasing an appropriate cabinet and monitor If you do not purchase a monitor from NEC Corporation of America provide a monitor that meets the system s requirements If you do not purchase the cabinet that NEC Corporation of America refere...

Page 12: ...upport necsam com servers ft See Appendix A System Specifications for Express5800 320Fc system specifications and the Express5800 320Fc Peripherals Site Planning Guide for specifications of other components Site Planning for Fault Tolerant Systems Consider the following specific fault tolerant features of Express5800 320Fc systems for site planning Lockstep technology means that the Express5800 32...

Page 13: ...document answer the following questions Planning for Optional Components The system contains four 10 100 1000 megabits per second Mbps Ethernet ports Will your system additionally include any of the following PCI adapters for network communications If so indicate how many of each and plan network connections for all Ethernet ports you will use ...

Page 14: ...stribution unit PDU Will you provide power from a UPS What are the AC power requirements of your system including all optional components Is the AC power service wired properly What are the lengths and types of the power cords that are provided with your system What type of receptacles do you need to provide Planning Space for Your System Will your system and its external components fit where you ...

Page 15: ...d cables are long enough to reach between their respective components and connectors Route all cables out of the way of foot traffic Working with Other Groups Have you provided your facilities group and contractors with the sketch and copies of the following Tables 4 2 4 3 and 4 4 worksheets for determining AC power requirements Tables 4 5 and 4 6 or Tables 4 7 and 4 8 worksheets for determining t...

Page 16: ...ceive your system you receive a printed copy of the Express5800 320Fc Installation Guide The software installation program lets you install an online copy of this document along with other Express5800 320Fc system documentation on your system You also have the option to install documentation on a remote system The Express5800 320Fc Help and Manuals folder on the Windows desktop contains these docu...

Page 17: ...System Documentation 1 7 page intentionally left blank Express5800 320Fc Site Planning Guide ...

Page 18: ...o allow the mounting rails to be fitted See Figure 2 1 The distance between the front and rear vertical rails is between 24 5 in and 30 in 62 23 cm and 76 20 cm The vertical mounting rails accept 10 32 cage nuts and mounting hardware The distance between the front vertical rails and the inside of the front door is at least 3 0 in 7 62 cm The distance between the rear of the system chassis and the ...

Page 19: ...net by either running them under the floor or placing them overhead in an overhead cable tray Air flows through the cabinet from front to back Filler panels cover any unused rack space to prevent air recirculation Vents are evenly distributed on the front and rear doors and comprise at least 63 of the surface area N O T E If your cabinet does not have vented front and rear doors you can remove the...

Page 20: ...Cabinet Requirements Cabinet and Monitor Requirements 2 3 Figure 2 1 Rail Clearance 1 Front vertical EIA rail 2 Accessory leg 3 Front of cabinet 0 5 inch 1 27 cm minimum 0 5 inch minimum msys182 1 2 3 ...

Page 21: ...of America make sure that The monitor accepts universal 100 240 VAC 50 60 Hz power The VGA cable has a 15 pin D sub connector The power cord for the monitor is long enough to reach the power source The plug type on the power cord is compatible with the external power source at the site Use the keyboard and mouse provided by NEC Corporation of America ...

Page 22: ...ure and humidity levels and has a thermometer and humidistat to monitor room temperature and humidity Is as free of dust as possible Dust buildup in the system can impede air circulation and heat transfer causing components to become less reliable as the ambient temperature rises Provides a table or desktop for external devices such as a telephone keyboard and mouse Provides cutouts in the floor f...

Page 23: ...g for service Ethernet jacks switches or hubs as needed Two electrically separate grounded AC wall outlets or a UPS and a wall outlet within reach of the power cords from the system or PDUs and additional outlets for any components that do not connect to a PDU Make sure that cables you plan to connect to the system are long enough to reach between the system and external components or connections ...

Page 24: ...quire at least two separate and independent AC power sources an A side power source and a B side power source that provide power to the system s power receptacles labeled respectively A and B Either source must be capable of continuing to provide power if power to the other source is lost The A side power source provides power to components that do not require two sources of power a KVM switch If ...

Page 25: ...urce In Table 4 3 determine the power requirements at the B side power source In Table 4 4 determine the power requirements for components outside of the cabinet These components can share a power source with the A side or B side components To determine power requirements Provide information in Tables 4 2 4 3 and 4 4 as follows 1 In the Quantity column write the number of each type of component 2 ...

Page 26: ...50 KVM switch x 20 TOTAL A SIDE POWER REQUIREMENTS Table 4 3 Worksheet for Determining B Side Power Requirements System Component Quantity Power Watts AC Power Extended TOTAL B SIDE POWER REQUIREMENTS Table 4 4 Worksheet for Determining External Power Requirements System Component Quantity Power Watts AC Power Extended Other external components TOTAL EXTERNAL POWER REQUIREMENTS Express5800 320Fc L...

Page 27: ...the cabinet use Tables 4 7 and 4 8 to determine the number of power outlets required outside the cabinet 1 In the Quantity column write the number of each type of component 2 Multiply the value in the Quantity column by the value in the Outlets column and enter the total in the Subtotal column 3 Add the values in the Subtotal column and enter the sum next to TOTAL NUMBER OF A SIDE POWER OUTLETS an...

Page 28: ...trical separation between the two power sources the less likely they will both fail at the same time Due to redundancy in Express5800 320Fc systems power to either side of the system keeps the system in operation although the system is no longer fault tolerant with regard to power Figure 4 1 shows how to connect a pedestal system directly to two separate power sources Table 4 7 Worksheet A Side Ex...

Page 29: ... all power cords out of the way of foot traffic Power cords described as Domestic are made with American Wire Gauge AWG cordage and are intended for use in North America Refer to UL 62 and CSA C22 2 No 49 Power cords described as International are made with International Harmonized cordage and are intended for use outside of North America 1 A side system power cord 2 B side system power cord 3 AC ...

Page 30: ...rd IEC 60309 formerly IEC 309 16A 250V 4 5m B50153 North America Chicago NEMA 5 15 15A 127V 7 ft B50101 North America domestic NEMA 5 15 15A 127V 15 ft B50104 Australia AS NZS 3112 1993 10A 250V 4 5m B50124 China GB1002 1996 10A 250V 4 5m B50162 Europe Continental CEE 7 VII 16A 250V 4 5m B50112 Israel SI 32 1971 16A 250V 4 5m B50132 Italy CEI23 16 10A 250V 4 5m B50136 Japan NEMA 5 15 15A 127V 15 f...

Page 31: ... AC power source or to the APC Smart UPS and APC Symmetra UPS models Table 4 12 describes the black power jumper cables that are provided to connect Express5800 320Fc systems to PDUs North America Domestic and Japan 250V NEMA L6 20 to IEC 60320 C13 15 ft 4 5m B50161 International 250V IEC 320 C14 to IEC 60320 C13 3 5m B50301 Table 4 10 Systems Power Cords to a UPS Locale Voltage Rating Plug Types ...

Page 32: ...156 International IEC 60320 C19 to IEC 60309 20A 250V 50 60 Hz 15 ft 4 5m B50154 Table 4 12 System Power Jumper Cables to a PDU Length Rating Plug Type to System Plug Type to PDU Marketing ID 2 0m 10A 250V IEC 320 C13 IEC 60320 formerly IEC 320 C14 B50502 Table 4 13 Power Cords for Optional Components Locale Rating Plug Type Length Marketing ID North America and Japan 15A 120V NEMA 5 15 7 ft B501 ...

Page 33: ...250V AS NZS 3112 1993 2 5m B501 21 South Africa 13A 250V SABS164 1 1992 ZA 3 2 5m B501 49 Switzerland 10A 250V SEV 1011 S24507 2 5m B501 37 United Kingdom 13A 250V BS1363 A 2 5m B501 13 Table 4 13 Power Cords for Optional Components Continued Locale Rating Plug Type Length Marketing ID ...

Page 34: ...n APC for use with Express5800 320Fc systems The qualifiedAPC Symmetra and APC Smart UPS models are listed in Tables 5 1 and 5 3 N O T E Site planning information for the UPS which you must supply is of a general nature only Do not rely exclusively on the UPS information in this document Contact APC at http www apcc com for detailed UPS specifications documentation and ordering information Table 5...

Page 35: ... monitors the UPS for an imminent power loss and initiates a shutdown of the system before power is lost Connecting Power to Systems PDUs and a UPS When you plan for PDUs note the following Only the top PDU is connected to the UPS The bottom PDU is connected directly to an AC power main The UPS can be connected to the same AC power main that the bottom PDU is connected to or the UPS can be connect...

Page 36: ... Connecting a System Directly to a UPS You can connect the A side power connectors of your system directly to a UPS as shown in Figure 5 2 1 A side PDU 2 B side PDU 3 B side system power cables black 4 A side system power cables gray 5 PDU power cords 6 UPS 7 UPS power cord 8 AC power outlets 9 AC power mains distribution circuit breaker maximum of 20A 8 8 5 4 7 5 2 asys003 9 9 3 1 3 4 6 ...

Page 37: ... 2 shows how to connect a UPS to pedestal Express5800 320Fc systems Figure 5 2 Pedestal Systems A Side Power Connected Directly to a UPS 1 B side system power cord 2 A side system power cord 3 UPS 4 UPS power cord 5 AC power outlets 6 Circuit breakers maximum of 20A asys005 5 2 6 5 6 3 4 1 ...

Page 38: ...s Ethernet PCI adapters are typically supplied in pairs and teamed in software for fault tolerance Each member of the pair requires a cable W A R N I N G Make sure Ethernet cables can be routed out of the way of foot traffic Table 6 1 describes the Ethernet cables you must supply Be sure to provide a cable of sufficient length for the distance between the system and a wall jack or hub N O T E See ...

Page 39: ...TIA 568 B standard For connections to an Ethernet hub or switch provide a straight through cable For 100 or 1000 Mbps fast Ethernet operation provide full duplex or Category 5 Ethernet cables The maximum allowable distance from an Ethernet port to a switch or a hub is 100 meters 328 ft 10 100 1000 Mbps system Ethernet port 2 or 4 Dual port 10 100 1000Base T Ethernet PCI Adapter gigabit copper adap...

Page 40: ...tem Specifications Figure A 1 shows the front of a pedestal Express5800 320Fc system its bezel pulled forward Figure A 2 shows the rear of a typical pedestal Express5800 320Fc system and Figure A 3 shows the rear of a pedestal Express5800 320Fc systems specifying the locations of the connectors at the back of the system Table A 1 lists specifications for the pedestal Express5800 320Fc system ...

Page 41: ...System Specifications A 2 Express5800 320Fc Site Planning Guide Figure A 1 Pedestal System Front View ...

Page 42: ...Figure A 3 Pedestal Express5800 320Fc systems Rear View 1 PCI slot 3 2 PCI slot 2 3 PCI slot 1 4 System 10 100 1000 Mbps Ethernet ports 4 5 USB ports 3 6 VGA monitor port 7 Serial COM ports 2 8 Power receptacles 2 9 VTM 10 100 Mbps Ethernet ports 2 4 6 5 7 8 3 1 2 9 ...

Page 43: ...31 38 in 79 71 cm Weight including 8 DIMMS 4 processors and 6 disks Two enclosures 110 lb 49 9 kg fully loaded Case 68 lb 30 84 kg Environmental Operating temperature 41 F to 95 F 5 C to 35 C For every 800 ft 243 8m above 2 000 ft 609 6m lower the maximum operating temperature 35 C by 1 C Storage temperature 38 F to 140 F 40 C to 60 C Operating altitude 0 ft to 10 000 ft 0m to 3 048m Maximum rate ...

Page 44: ...closure s t r o p t e n r e h t E s p b M 0 0 0 1 0 0 1 0 1 r u o F s t r o P Two AC power connectors one VGA port two serial ports and three USB ports PCI slots Express5800 320Fc systems One user configurable low profile PCI adapter slot operating at 64 bits and 100 MHz in each CPU I O enclosure you can add two full height PCI adapter slots in each CPU I O enclosure M T V e l u d o M n a i c i n ...

Page 45: ...hat feeds the PDUs To connect a single system to power use 20A or less circuit breakers in each power distribution branch that feeds the systems Grounding Considerations The system obtains an earth reference ground through the power cords attached to the system Similarly each peripheral device connected to the system obtains ground through its power cord For each peripheral device you must ensure ...

Page 46: ... same earth reference ground Each earth reference ground such as the system base ground is returned separately to a common point where a zero volt 0V earth ground exists The star ground ensures that all equipment is at the same potential and that no noise or safety problems associated with an unpredictable or uncharacterized grounding system will occur Figure B 1 Star Ground Example 1 To monitor 2...

Page 47: ...n phase to phase Figure B 8 illustrates a three phase 380V AC Y or source circuit connection phase to neutral In the diagrams in this appendix the power inputs for an Express5800 320Fc system are labeled X and Y as shown in Figure B 2 to eliminate any ambiguities in the nomenclature For single phase applications the X input is connected to the L Line hot input and the Y input is connected to the N...

Page 48: ...re B 3 shows a single phase 120 volts AC circuit connection Note that this application requires a single pole circuit breaker Figure B 3 Single Phase 120 Volts AC Circuit Connection Circuit A or B X Y G PE To power input A or B Wall Power Cord L N G PE 120V 0V 15A Maximum ...

Page 49: ...a single phase 240 volts AC circuit connection Note that this application requires a single pole circuit breaker Figure B 4 Single Phase 240 Volts AC Circuit Connection Circuit A or B X Y G PE To power input A or B Wall Power Cord L N G PE 0V Single system 20A maximum 240V PDU 30A maximum ...

Page 50: ...e 120 240 volts AC circuit connection Note that this application requires a double pole circuit breaker Figure B 5 Split Phase 120 240 Volts AC Circuit Connection Circuit A or B X Y G PE To power input A or B Wall Power Cord L1 L2 N G PE 240V 120V 0V 120V Single system 20A maximum PDU 30A maximum ...

Page 51: ...source connection Note that the X input on the system can be connected from L1 L2 or L3 This application requires a single pole circuit breaker Figure B 6 Three Phase 208 Volts AC Y or Source Circuit Connection Phase to Neutral Circuit A or B X Y G PE To power input A or B Wall Power Cord L1 L2 L3 N G PE 120V 120V 208V 208V 120V 0V Single system 20A maximum PDU 30A maximum ...

Page 52: ...n Note that the X and Y inputs on the system can be connected from L1 and L2 L2 and L3 or L1 and L3 This application requires a double pole circuit breaker Figure B 7 Three Phase 208 Volts AC Y or Source Circuit Connection Phase to Phase Circuit A or B 120V X Y G PE To power input A or B Wall Power Cord L1 L2 L3 N G PE 208V 208V 120V 0V 120V Single system 20A maximum PDU 30A maximum ...

Page 53: ... application requires a single pole circuit breaker Figure B 8 Three Phase 380V AC Y or Source Circuit Connection Phase to Neutral Electrical Power Connectors Table B 1 describes the connectors that NEC Solutions America Inc uses to connect an Express5800 320Fc system and peripheral devices to AC power outlets Circuit A or B 220V X Y G PE To power input A or B Wall Power Cord L1 L2 L3 N G PE 220V ...

Page 54: ...wer Outlets Connector Configuration Rating Description NEMA L6 20 20A 250 volts AC 2 pole 3 wire NEMA 5 15 15A 125 volts AC 2 pole 3 wire NEMA L6 30 30A 250 volts AC 2 pole 3 wire CEE 7 VII 20A 250 volts AC 2 pole 3 wire CEI 23 16 16A 250 volts AC 2 pole 3 wire SI 32 1971 16A 250 volts AC 2 pole 3 wire ...

Page 55: ...e SABS 164 1 1992 16A 250 volts AC 2 pole 3 wire BS 1363 A 13A 250 volts AC 2 pole 3 wire SEV 1011 S24507 10A 250 volts AC 2 pole 3 wire AS NZS 3112 1993 15A 250 volts AC 2 pole 3 wire SAA 3 15 AS NZS 3112 1993 15A 250 volts AC 2 pole 3 wire Table B 1 Connectors for AC Power Outlets Continued Connector Configuration Rating Description ...

Page 56: ...ctrical Power Connectors B 12 Express5800 320Fc Site Planning Guide GB1002 1996 10A 250 volts AC 2 pole 3 wire Table B 1 Connectors for AC Power Outlets Continued Connector Configuration Rating Description ...

Page 57: ... install all wiring including power and communications cables in compliance with local and national electrical code in the United States national electrical code NFPA 70 In addition you must use shielded communications cables to remain in compliance with Federal Communications Commission FCC and other international Electromagnetic compatibility EMC regulations 3 All EMI emissions compliance tests ...

Page 58: ...logy Equipment Japan Table C 2 Immunity Standards Standard Description Country Region EN 50082 1 Generic Immunity Standard Electromagnetic Compatibility Residential Commercial and Light Industrial European Union EN 55024 Limits and methods of measurement of immunity characteristics of Information Technology Equipment European Union Table C 3 Safety Standards Standard Description Country Region UL ...

Page 59: ...Standards Compliance Standards Compliance C 3 VCCI Note BSMI Note ...

Page 60: ...Standards Compliance C 4 Express5800 320Fc Site Planning Guide ...

Page 61: ... planning information B 1 wiring diagrams B 3 compliance standards C 1 connectors AC B 9 cooling requirements 3 1 See also environmental requirements 3 1 D documentation ordering 1 6 E earth reference ground B 1 electrical connectors B 9 electrical grounding B 1 electrical wiring B 1 electromagnetic interference C 2 environmental requirements maximum rate of temperature change A 5 operating humidi...

Page 62: ...om requirements 3 1 S SAA 3 15 AS NZS 3112 1993 connector B 11 SABS 164 1 1992 connector B 11 safety regulations C 2 SEV 1011 S24507 connector B 11 SI 32 1971 connector B 10 single phase circuit connections 120 V AC B 4 240 V AC B 5 site planning checklist 1 2 space planning 3 1 specifications AC power 4 2 pedestal system A 1 split phase circuit connections 120 240 V AC B 6 standards compliance C ...

Reviews: