Electrical Circuit and Wiring Information
B-1
Appendix B
Electrical Circuit and Wiring Information
B-
For electrical circuit and wiring information that you need to provide to the contractor
and/or facilities personnel responsible for wiring the power at the system installation
site, see:
•
“Fault Protection Requirements” on page B-1
•
“Grounding Considerations” on page B-1
•
“Circuit Wiring Diagrams” on page B-3
•
“Electrical Power Connectors” on page B-9
Fault Protection Requirements
Each enclosure in Express5800/320
Fc
systems contains internal fault/overload
current protection. However, the system relies on the
power distribution system
at your site for protection against potential faults in the power
cords and the wiring in
the system base.
•
If you are using a pair of PDUs in the cabinet, use 30A or less circuit breakers in
each power distribution branch that feeds the PDUs.
•
To connect a single system to power, use 20A or less circuit breakers in each power
distribution branch that feeds the systems.
Grounding Considerations
The system obtains an earth reference ground through the power cords attached to the
system. Similarly, each peripheral device connected to the system obtains ground
through its power cord. For each peripheral device, you
must
ensure that a
high-integrity safety-ground conductor is installed as part of the wiring system (in
accordance with U.S. national electric code NFPA 70 or the equivalent). The
international safety standard (EN60950) for electronic data processing (EDP)
equipment also requires a ground conductor, but calls it a protective earth (PE) ground.
Depending upon local conditions, ground potentials may differ between the system
base and any peripheral devices connected to the system base. All grounds in the
system
must
return to the same reference point in the power distribution system, as
close as possible to
zero (0) volt potential
relative to earth reference ground. Earth
Summary of Contents for Active Upgrade Express5800/320Fc
Page 1: ...NEC Corporation of America 456 01723 000 Express5800 320Fc Site Planning Guide ...
Page 10: ...Preface x Express5800 320Fc Site Planning Guide ...
Page 17: ...System Documentation 1 7 page intentionally left blank Express5800 320Fc Site Planning Guide ...
Page 59: ...Standards Compliance Standards Compliance C 3 VCCI Note BSMI Note ...
Page 60: ...Standards Compliance C 4 Express5800 320Fc Site Planning Guide ...