Power supply (see available models) 

230Vac 

 10% or 12Vac/dc 

 

10% or 12…24Vac/dc 

Frequency 

50/60Hz 

Consumption 

2 VA 

Command outputs 

SPDT relay - capacity of the contact 250Vac 8A (2000VA) 

1

st

, 2

nd

 and 3

rd

 alarm threshold 

50, 100 and 300ppm

(1)

 of Carbon Monoxide 

Alarm threshold times at 

    50ppm

 

 

  100ppm

 

 

  300ppm 

between 60 and 90 minutes

 

between 10 and 40 minutes

 

 

   within 3 minutes 

Operational lifetime of the detector 

6 years from the date of manufacture (indicated on the 
detector) 

Max detectable area  

approx. 40 m

2

  

Visual warnings 

Green LED (power is on / warm-up) 

Yellow LED (sensor fail / general abnormality) 

Red LED (gas alarm) 

Audible alarms: 

 

 

 

 

 

     by a remote unit/detector 

Piezoelectric buzzer 85dB at 1m 

Protection Rating 

IP42 when correctly installed 

Product conformity standard 

      EMC Electromagnetic Compatibility 

            Low voltage (LVD) 

EN50291 

EMC 2014/30/EU 

– EN50270

 

LV 2014/35/EU 

– EN60335-1 

Operational room temperature 

-10...+40 °C  (storage 

–20…...+70 °C) 

Ambient humidity allowed: 

30... 90% RH (storage 0...+95% RH) (non condensing) 

Dimensions 

Mounting holes compatible with 503 type recessed mounting 
box

 

Maximum dimensions: 138 x 104 x 40 mm 

Enclosure 

ABS/PC UL94-V0 flame retardant 

(1) 

ppm =

 

parts per million of concentration of gas in the air. 

___________________________________________________________________________________________ 

Wiring diagrams: 

Example a): 

- Command of a solenoid valve (Normally Open); in this mode, when the alarm threshold is ex-

ceeded the solenoid valve and therefore the gas supply will close or an appropriate ventilation 

and/or alarm system will start up. 

Example b): 

- Command of a solenoid valve (Normally Closed) and of visual and audible alarms; in this mode, 

the solenoid valve and therefore the gas supply will close when the alarm threshold is exceed-

ed, if there is a power outage or if the actual solenoid valve connection is cut off. 

 

___________________________________________________________________________________________ 

This  product  has  been  developed  and  built  using  materials  and  processes  that  take  into  account  the  environ-
mental  issue.  Refer  to  the  following  notes  for  disposal  of  the  product  at the  end  of  its  life,  or  in case  of  its  re-
placement: 

-

 

for the purpose of disposal, this product is classified as an electrical and electronic device: do not dispose of 
it as household waste, in particular as regards the printed circuit 

-

 

comply with all local laws in force 

-

 

facilitate the reuse of basic materials as much as possible in order to minimize the environmental impact  

-

 

use  local  depots  and  waste  recycling  companies,  or  refer  to  the  supplier  or  manufacturer,  to  return  used 
products or to obtain further information on environmental compatibility and waste disposal 

-

 

The product packaging is reusable. Keep it for possible future use or in case of returning the product to the 
supplier. 

___________________________________________________________________________________________ 

Due to our policy of continuous product improvement, specifications are subject to change without notice. 

Technical 
specifications

 

Connection 
diagrams

 

Environmental 
Compatibiliy 
and Disposal

 

230Vac  or  12Vac/dc  or  12…24Vac/dc

 

L+

 

N -

 

a) 

ESN.F.O..

 

C

 

NC 

NA 

NO 

230Vac  or  12Vac/dc  or  12…24Vac/dc

 

L+

 

N -

 

b) 

ESN.F.O..

 

C

 

NC 

NA 

NC 