background image

 

rev. 05 of 15-01-20 / pag. 2 

___________________________________________________________________________________________ 

Ensure compliance with standards in force for electrical wiring. 
The devices must be connected to the mains and remain permanently powered. 
 Omnipolar disconnection must be included in the mains. 
The  installation  of  a  detector  must  not  be  a  substitute  for  the  correct  installation,  use  and  maintenance  of 
combustible gas appliances and equipment and for ventilation and exhaust systems for fumes. 
Carefully  read  the  instructions  and  electrical  wiring  diagrams  in  this  document  and  follow  them  to  the  letter. 
Keep this document in a safe place for future consultation. 
The device must be installed by qualified technicians. 
 
 

Installation 

Since carbon monoxide weighs the same as air, it will be concentrated near the same height as the appliance 
that manifests combustion defects or that is located in premises with insufficient ventilation. 
Install about 2 metres (minimum 1 metre, maximum 3 metres) from the gas-operated appliance and at standard 
face height of the occupants in those premises; example: 130…170cm in a kitchen, 50...100cm in a bedroom. 
The detector 

must not

 be installed: 

 

outdoors 

 

too close to stoves, cooking appliances and, more in general, to gas appliances 

 

near sinks and taps 

 

near exhaust hoods, windows, fans, or ventilation apertures. 

 

in areas where dirt and/or dust can clog the front grille of the detector 

 

where the temperature or humidity exceeds the detector's operating limits 

 

in closed spaces (behind curtains, inside cupboards etc.). 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
 

Commissioning 

Select the relay operational mode by positioning jumper E1 

 

E1 positioned towards A = continuous relay control

 

E1 positioned towards B = pulsed relay control (0.5s ON every 10s) 

 

Power  up  the  detector  and  make  sure  the  initial  operational  test,  the  display  of  the  firmware  version  and  the 

sensor warm-up is executed as indicated on the operational table. 

At the end of the warm-phase, the detector enters normal operation mode by pressing button S1 for at least 1 

second; check that the alarms act in conformity to what is indicated in the operational table and that the solenoid 

valve or other command and/or alarm device connected to the relay are correctly engaged. 

It is advisable to repeat the operational test at least once a year, or after a prolonged period of stoppage. 

If  other  test  methods  are  used  instead  of  the  one  described,  the  detector  may  generate  different,  unexpected 

responses. In particular, the use of inappropriate substances or vapours (alcohol or silicon-based solvents etc.) 

or in any case, high concentrations of test gases could cause permanent damage to the sensing element and 

may cause the detector to operate incorrectly. 

After the wiring is completed and the operational checks have been made, power down the detector, and tilt the 

front cover slightly downwards to fasten it onto the two clip-on points shown in the figure. 

Rotate the cover upwards, making sure that all three LEDs are centred. 

Press down firmly on the top of the cover and tighten the locking screw. 

Power up the detector and make sure the initial operational test, the display of the firmware version, the sensor 

warm-up and the passage to normal operation is executed correctly. 

 

___________________________________________________________________________________________ 

 

Installation and 
Commissioning

 

Power supply 

Configuration jumper E1 and 

test button S1 

8A / 250Vac relay output 

Piezoelectric buzzer 

Green LED

 

Power supply / 

Warm-up 

Yellow LED

 

Sensor Fail / Gen-

eral Abnormality 

Red LED

 

Alarm 

Electrochemical cell sensor 

(duration 6 years from date of 

manufacture) 

Cover

 

clip-on point 

Cover locking screws 

Reviews: