background image

Empowering you to work smarter 

NAVAC 

CONTENTS 

TECHNICAL SPECIFICATIONS···························································· 01 

SAFETY PRECAUTIONS •••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 01 

WORKING PRINCIPLES AND APPLICATION·········································· 02 

CONNECTING TO THE EQUIPMENT···················································· 03 

MACHINE PARTS AND FUNCTIONS····················································· 03

INSPECTIONS BEFORE OPERATION ••••••••••••••••••••••••••••••••••••••••••••••••••• 06

OPERATION PROCEDURES ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 06 

ROUTINE USE AND MAINTENANCE •••••••••••••••••••••••••••••••••••••••••••••••••••• 08

SPECIAL MAINTENANCE OPERATION················································· 10 

EXPLODED VIEW ••• ••• •• ••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••••• 12 

REPAIR PARTS LIST·········································································· 13 

TROUBLESHOOTING········································································ 14 

01 

Empowering you to work smarter 

NAVAC 

1. TECHNICAL SPECIFICATIONS 

R11,  R12,  R13,  R22,  R23,  R32,  R113,  R114,  R123,  R124,  R134a,  R290, 

R401A,  R401B,  R402A,  R402B,  R404A,  R406A,  R407A,  R407C,  R408A, 

Compatible Refrigerants 

R409A,  R410A,  R413A,  R414B,  R416a,  R417A,  R420A,  R422A,  R422B 

R422D,  R424A,  R426A,  R427A,  R428A,  R434A,  R437A,  R442A,  R448A, 

R449AR450A,  R452A,  R454B,  R502,  R507A,  R508B,  R513A,  R600a,  R728, 

R7 44,  R1234yf 

Power Supply 

115V / 60Hz 

Evacuation Rate 

6 CFM 

Charging Rate 

4 lbs/min 

Motor Power 

1/3 HP 

Current 

3.2A 

Operating Temperature 

30-104

°

Dimension 

19.7" X 10" X 14.5" 

Weight 

39 lbs 

2. SAFETY PRECAUTIONS 

Safety instructions 

1. This evacuation and charging machine designed for use only by trained HVACR professionals, and 

can be damaged or dangerous if operated incorrectly. 

2. For your safety and correct operation, please read the operation manual carefully before use. 
3. Never connect vcharging machine to a pressurized system, and always verify system is at atmospheric 

pressure or below before connecting hoses to an HVACR system. 

4. Protective gloves and goggles should be worn during operation in case refrigerant gas or liquid 

comes in contact with skin or eyes. 

5. Do not smoke while operating evacuation or charging equipment. 
6. Do not use machine near flammable gases, open flames, or other ignition source. 
7. Please do not use equipment in direct sun or in rain, cover if needed, leaving adequate room for 

ventilation. 

8. Always make sure the equipment has good ventilation. 

Precautions: 

1. The smart refrigerant charging machine is for use with air conditioning and refrigeration systems 

only. 

2. The red high-pressure hose is connected to the high pressure (liquid) valve on NC-R systems and 

blue low pressure hose to the low-pressure (suction) valve. 

3. Before operation, verify the type of refrigerant used to insure compatibility. 

02 

Summary of Contents for NRC62D

Page 1: ...5 Commonwealth Ave Woburn MA 01801 Phone 781 665 1400 Toll Free 1 800 517 8431 Visit us at www TestEquipmentDepot com...

Page 2: ...ation and charging machine designed for use only by trained HVACR professionals and can be damaged or dangerous if operated incorrectly 2 For your safety and correct operation please read the operatio...

Page 3: ...ant has been evacuated Precautions at operation and use of refrigerant Under the normalcircumstances refrigerant is apressurizedliquid For ease of use and transportation it is stored in a certified cy...

Page 4: ...splay area A2 Current procedure Status and Warning E1 High temperature probe error E2 Low temperature probe error E3 Vacuum sensor error If these errors occur contact our dealer or technical support F...

Page 5: ...sure connection on the charging machine and the other end with the suction line on the equipment Connect one end of the red hose with HP high pressure connection on the charging machine and the other...

Page 6: ...vel will degrade performance of the pump while too high oil level will cause a large quantity of oil mist to discharge fromthe oilfill port 09 Empowering you to work smarter N AV AC Replace vacuum pum...

Page 7: ...bluetooth button 11 Empowering you to work smarter N AYf AC 9 1 3 Process for synchronizing wireless communication 1 Make sure the scale is not weight loaded Turn on the charging machine and scale If...

Page 8: ...hen HT LT signals and probe yellow flash it meansnot sync 3 Go to Main Menu Initial Setup High Temp Sensor Bluetooth Low Temp Sensor Bluetooth Sync Press ENTER tooperate 4_ If sync succeed within 1 mi...

Page 9: ...Return ValveAssy 1 17 CRP 17 Dustproof Screen 1 18 CRP 18 Vacuum Pump 1 19 CRP 19 Rubber Feet I 4 20 CRP 20 Rubber Feet II 3 21 CRP 21 Base PlateAssy 1 22 CRP 22 Rubber Buffer 5 23 CRP 23 Valve Body...

Page 10: ...is insufficient vacuum mode 4 The copper connection hose leaks Check the connection hose 5 Components on the pump worn out due Check and repair the pump or replace it to long hours of use with a new...

Reviews: