![background image](http://html2.mh-extra.com/html/national-instruments/scxi-1127/scxi-1127_getting-started-manual_4533654029.webp)
©
National Instruments Corporation
29
NI Switches Getting Started Guide
Example 2
SCXI-1000 chassis
SCXI-1359 2-slot backplane adapter behind Slots 3 and 4
SCXI-1127 (250 V, CAT II) in Slot 4
SCXI-1129 (150 V, CAT I) in Slot 2
The SCXI-1127 does not share the HVAB with the SCXI-1129. Therefore,
the SCXI-1127 can operate at the full rating (250 V, CAT II).
Example 3
SCXI-1000 chassis
SCXI-1359 2-slot backplane adapter behind Slots 3 and 4
SCXI-1127 (250 V, CAT II) in Slot 4
SCXI-1190 (30 V, CAT I) in Slot 3
The SCXI-1190 does not have a HVAB connector. Therefore, the
SCXI-1127 can operate at the full rating (250 V, CAT II).
10. Programming the Switch Modules
You can operate the switch module in one of the following three ways:
•
Interactively using the NI-SWITCH Soft Front Panel
•
Programming using the NI-SWITCH API
•
Programming using the NI-DAQmx API
NI-SWITCH Soft Front Panel (SFP)
The NI-SWITCH SFP is an interactive tool you use to test the basic
functionality of the switch, become familiar with its operation, and
troubleshoot your applications. The NI-SWITCH SFP supports all
NI switch modules.
You can launch the NI-SWITCH SFP from
Program Files»National
Instruments»NI-SWITCH»NI-SWITCH Soft Front Panel
.
NI-SWITCH API
The NI-SWITCH API includes a set of operations and attributes that use all
the functionality of the switch, including configuration, control, and other
module-specific functions. The NI-SWITCH API supports all NI switch
modules.