![background image](http://html2.mh-extra.com/html/national-instruments/ni-9514/ni-9514_operating-instructions-and-specifications_3393023029.webp)
28
|
ni.com
|
NI 9514Operating Instructions and Specifications
Limit or home input configured for sinking
Digital logic levels, OFF state
Input voltage ........................
≤
5 V
Input current.........................
≤
250 µA
Digital logic levels, ON state
Input voltage ........................ 11 to 30 V
Input current.........................
≥
2 mA
Limit or home input configured for sourcing
Digital logic levels, OFF state
Input voltage ........................ 11 to 30 V
Input current.........................
≤
1 mA
Digital logic levels, ON state
Input voltage ........................
≤
5 V
Input current.........................
≥
2 mA
Min pulse width
1
............................... 50 µs
1
Assumes the minimum filter setting. Refer to the
SoftMotion Module
book of the
LabVIEW Help
for more information about filter options.
Summary of Contents for NI 9514