Figure 4. DIN Terminal Block Pinout
1
2
3
1. Protective earth
2. Line
3. Neutral
7.
Ensure that the protective earth wire is connected to the green/yellow terminal and has
more slack than the power wires so that the grounding terminal always disconnects last.
8.
Tighten the PG16 dome nut with a 24 mm socket or wrench to a torque of 3.33 N · m
(29.5 lb · in.) to provide strain relief and weather resistance for the cable.
Using the Desiccant Kit
If your application is outdoors (non-weather-protected according to IEC 60721-3-4), or if the
device might be directly exposed to an outdoor climate (partially weather-protected according
to IEC 60721-3-3, 3K4 or greater), you must use a desiccant pack from the desiccant kit (part
number 787006-10) to meet the humidity specifications. Replace the desiccant kit after two
years of use.
Notice
Do not put a load on the device door while it is open.