National Instruments Corp.

7

FP-DI-330

Isolation and Safety Guidelines

Caution

Read the following information before 

attempting to connect ANY circuits which may contain 
hazardous voltages to the FP-DI-330.

This section describes the isolation of the FP-DI-330 and its 
compliance with international safety standards. The field wiring 
connections of the FP-DI-330 are isolated from the

 

backplane 

provided by the terminal base with an optical and galvanic isolation 
barrier designed and tested to provide protection against fault 
voltages of up to 3000 Vrms. In addition, the FP-DI-330 provides 
double insulation (compliant to IEC 1010-1) for working common 
mode voltages of 250 Vrms. Safety standards (such as those 
published by UL and IEC) require the use of double insulation 
between hazardous voltages and any human-accessible parts or 
circuits. You should never attempt to use any isolation product 
between human accessible parts (such as DIN rails or monitoring 
stations) and circuits which may be at hazardous potentials under 
normal conditions, unless the product is specifically designed 
(as the FP-DI-330 is) for such an application.

Even when a product like the FP-DI-330 is used in applications 
with hazardous potentials, follow these guidelines to ensure a safe 
total system.

The safety isolation of the FP-DI-330 is from input to output, 
not between channels on the same module. If any of the 
channels on a module are wired at a hazardous potential, 
ensure that all other devices or circuits connected to that 
module are properly insulated from human contact.

Do not share the external supply voltages (V and C on the 
terminal base) with other devices (including other FieldPoint 
devices) unless those devices are also isolated from human 
contact.

As with any hazardous voltage wiring, ensure that all wiring 
and connections meet with applicable electrical codes or 
common sense practices. Mount terminal bases in an area, 
position, or cabinet that prevents accidental or unauthorized 
access to wiring with hazardous voltages.

The isolation of the FP-DI-330 is certified as double insulated 
for normal operating voltages of 250 Vrms. Do not use the 
FP-DI-330 as the sole isolating barrier between human contact 
and working voltages of more than 250 Vrms.

Summary of Contents for FieldPoint FP-DI-330

Page 1: ...o the user manual for the particular FieldPoint network module you are using with the FP DI 330 Features The FP DI 330 is a FieldPoint discrete input module with the following features Eight discrete input channels Universal inputs work with any voltage from 5 V TTL level up to 250 VDC VAC Compatible with sourcing sinking or power sensing applications On Off LED indicators Hot plug and play operat...

Page 2: ...mly seated Figure 1 Module Installation Diagram Field Wiring The terminal base provides connections for each of the eight input channels and an external supply to power field devices Each channel can be wired for use with either a sourcing or sinking output device or to sense whether power is being delivered to a load Figure 2 shows examples of these basic wiring connections The connection of an e...

Page 3: ...COM INb INa INb INa INb INa INb INa Vsup Vsup Vsup Vsup COM COM COM COM INb Power Supply for Transducers 5 250 Volts Sinking NPN Open Collector 3 Wire Devices Powered From FP DI 330 Terminals Sourcing PNP Open Emitter Sinking Sourcing Sensing Power Applied to a Load V C Devices Powered Externally Load ...

Page 4: ... isolator registering as an ON condition The current limiting circuitry limits the amount of current flow to 1 5 mA even when the applied voltage is as high as 250 Vrms Each input is functionally isolated from the other inputs and may be wired independently but this is not a safety isolation Warning Do not mix circuits with hazardous voltages and human accessible circuits on the same module For mo...

Page 5: ...e not guaranteed to be either off or on The typical threshold voltage is 1 5 V Figure 2 shows connections to sourcing output devices sinking output devices and powered loads These devices should have OFF state leakage currents of less than 350 µA to ensure that they do not provide false ON state readings to the FP DI 330 The filter on the FP DI 330 input stages provides for a delay of approximatel...

Page 6: ...ed ON voltages described above the FP DI 330 may register the state as either ON OFF or as a signal alternating between ON and OFF Status Indicators Figure 4 shows the module label and status indicators You can remove the insertable label to see wiring diagrams for the input channels Figure 4 Status Indicators After the module has been inserted into a terminal base and power is applied the green P...

Page 7: ...nder normal conditions unless the product is specifically designed as the FP DI 330 is for such an application Even when a product like the FP DI 330 is used in applications with hazardous potentials follow these guidelines to ensure a safe total system The safety isolation of the FP DI 330 is from input to output not between channels on the same module If any of the channels on a module are wired...

Page 8: ... 1 ms Isolation 3 000 Vrms Safety isolation working voltage 250 Vrms designed per IEC 1010 as double insulated Physical Indicators Green POWER and READY indicators 8 green input state indicators Weight 130 g 4 5 oz Power Requirements Power from network module 200 mW Environment Operating temperature 40 to 70 C Storage temperature 55 to 100 C Relative humidity 5 to 90 non condensing Logic Level Min...

Page 9: ... insulation for 250 Vrms working isolation installation category II EMC Directive Immunity EN 50082 1 1994 Emissions EN 55011 1991 Group I Class A at 10 meters Mechanical Dimensions Figure 5 shows the mechanical dimensions of the FP DI 330 Dimensions are given in inches millimeters Figure 5 Mechanical Dimensions 4 31 109 5 3 60 91 44 4 22 107 19 ...