Mounting Requirements
Your installation must meet the following requirements for cooling and cabling
clearance.
Allow 25.4 mm (1.00 in.) on the top and the bottom of the cRIO-9063 for air
circulation, as shown in the following figure.
Figure 9.
cRIO-9063 Cooling Dimensions
25.4 mm (1.00 in.)
25.4 mm (1.00 in.)
Allow the appropriate space in front of C Series modules for cabling clearance, as
shown in the following figure. The different connector types on C Series modules
require different cabling clearances. For a complete list of cabling clearances for C
and enter the Info Code crioconn.
Figure 10.
cRIO-9063 Cabling Clearance
Cabling Clearance
50.8 mm (2.00 in.)
29.1 mm
(1.14 in.)
50.8 mm
(2.00 in.)
Ambient Temperature
Measure the ambient temperature at each side of the cRIO-9063, 63.5 mm (2.50 in.)
from the side and 25.4 mm (1.00 in.) forward from the rear of the cRIO-9063, as
shown in the following figure.