Figure 2.

 cRIO-9038 Front Panel

1

2

3

4

5

6

8

9

11

14

13

12

10

7

1. LEDs
2. Ethernet Ports
3. Power Connector
4. SD LEDs
5. SD Card Removable Storage
6. Ground Screw
7. USER1 Button

8. RS-232 Serial Port
9. RS-485/422 (DTE) Serial Port
10. USB Host Ports
11. Mini DisplayPort
12. Cable Retention Mounts
13. USB Device Port
14. Power and Reset Buttons

Connecting the cRIO-9038 to Ground

You must connect the cRIO-9038 grounding terminal to the grounding electrode system of the
facility.

What to Use

Ring lug

Wire, 1.3 mm

2

 (16 AWG) or larger

Screwdriver, Phillips #2

What to Do

Complete the following steps to ground the cRIO-9038.
1.

Attach the ring lug to the wire.

2.

Remove the grounding screw from the grounding terminal on the cRIO-9038.

3.

Attach the ring lug to the grounding terminal.

4.

Tighten the grounding screw to 0.5 N · m (4.4 lb · in.) of torque.

5.

Attach the other end of the wire to the grounding electrode system of your facility using a
method that is appropriate for your application.

NI cRIO-9038 Getting Started Guide

  | 

© National Instruments

  | 

7

Summary of Contents for cRIO-9038

Page 1: ...w to begin using the National Instruments cRIO 9038 Safety Guidelines Caution Do not operate the cRIO 9038 in a manner not specified in this document Product misuse can result in a hazard You can comp...

Page 2: ...nclosure rated to at least IP54 as defined by IEC EN 60079 15 Caution Do not insert or remove SD cards unless power has been switched off or the area is known to be nonhazardous Caution The USB host p...

Page 3: ...ral device or test object or if the product is used in residential or commercial areas To minimize interference with radio and television reception and prevent unacceptable performance degradation ins...

Page 4: ...ts In addition take precautions when designing selecting and installing measurement probes and cables to ensure that the desired EMC performance is attained Preparing the Environment Ensure that the e...

Page 5: ...IO Device Drivers Media 5 Getting Started Guide Installing Software on the Host Computer Before using the cRIO 9038 you must install the following application software and device drivers on the host c...

Page 6: ...n the C Series module 3 Align the C Series module with a slot and seat it in the slot until the latches lock in place Removing C Series Modules Verify that power is not connected to the I O connector...

Page 7: ...rminal to the grounding electrode system of the facility What to Use Ring lug Wire 1 3 mm2 16 AWG or larger Screwdriver Phillips 2 What to Do Complete the following steps to ground the cRIO 9038 1 Att...

Page 8: ...038 has a primary power input V1 and a secondary power input V2 The POWER LED on the cRIO 9038 indicates which power input is in use as shown in the following table Table 2 POWER LED Indicators LED Co...

Page 9: ...tive leads of the power supply as shown in the following figure Figure 3 Installing a Ferrite on the Power Leads 2 1 1 Pass the leads through the ferrite twice leaving 50 mm to 75 mm 2 in to 3 in betw...

Page 10: ...cRIO 9038 When you power on the cRIO 9038 for the first time the device boots into safe mode The POWER LED illuminates the STATUS LED illuminates briefly and then the STATUS LED blinks twice every few...

Page 11: ...system password Note The default username for the cRIO 9038 is admin There is no default password for the cRIO 9038 so you must leave the password field blank when logging in until you set a system pa...

Page 12: ...odule Tip You can use this wizard at anytime to install additional software 7 Click Next 8 Verify that the summary of software to install is correct 9 Click Next to start the installation 10 Click Fin...

Page 13: ...System IP Configuration 1 Put the cRIO 9038 in safe mode and enable the RS 232 serial port by holding the RESET button down for 5 seconds The STATUS LED starts blinking three times every few seconds...

Page 14: ...d RESET button for 5 s Press and hold RESET button for 5 s Run Mode Safe Mode Press and hold RESET button for 5 s Press and hold RESET button for 5 s Press and hold RESET button for 5 s Press and hold...

Page 15: ...r longer than five seconds or by enabling safe mode in MAX Refer to the Measurement Automation Explorer MAX Help for information about safe mode Blinks four times and pauses The cRIO 9038 is in safe m...

Page 16: ...eshooting and application development self help resources to email and phone assistance from NI Application Engineers Visit ni com services for NI Factory Installation Services repairs extended warran...

Page 17: ...create your service request at ni com support or dial 1 866 ASK MYNI 275 6964 For telephone support outside the United States visit the Worldwide Offices section of ni com niglobal to access the bran...

Page 18: ...party legal notices in the readme file for your NI product Refer to the Export Compliance Information at ni com legal export compliance for the NI global trade compliance policy and how to obtain rel...

Reviews: