3G and is suitable for use in Zone 2 hazardous locations, in ambient temperatures of -40 °C ≤
Ta ≤ 70 °C.
Caution
You must make sure that transient disturbances do not exceed 140% of
the rated voltage.
Caution
The system shall only be used in an area of not more than Pollution
Degree 2, as defined in IEC 60664-1.
Caution
The system shall be mounted in an ATEX/IECEx-certified enclosure with
a minimum ingress protection rating of at least IP54 as defined in IEC/EN 60079-15.
Caution
The enclosure must have a door or cover accessible only by the use of a
tool.
Electromagnetic Compatibility Guidelines
This product was tested and complies with the regulatory requirements and limits for
electromagnetic compatibility (EMC) stated in the product specifications. These requirements
and limits provide reasonable protection against harmful interference when the product is
operated in the intended operational electromagnetic environment.
This product is intended for use in industrial locations. However, harmful interference may
occur in some installations, when the product is connected to a peripheral device or test object,
or if the product is used in residential or commercial areas. To minimize interference with
radio and television reception and prevent unacceptable performance degradation, install and
use this product in strict accordance with the instructions in the product documentation.
Furthermore, any changes or modifications to the product not expressly approved by National
Instruments could void your authority to operate it under your local regulatory rules.
Caution
To ensure the specified EMC performance, operate this product only with
shielded cables and accessories. The DC power input cables may be unshielded.
Caution
To ensure the specified EMC performance, you must use an isolated cable
with the RS-485 serial port, such as NI part number 184428-01.
Caution
To ensure the specified EMC performance, the length of any cable
connected to the video and V2 ports must be no longer than 3 m (10 ft). The length
of any cable connected to the RS-232 and RS-485 ports must be no longer than
30 m (100 ft). The length of any cable connected to the USB host ports must be no
longer than 5 m (16 ft).
Caution
The USB device port is intended only for use in device configuration,
application deployment, debug, and maintenance.