3. Select
Measurement & Automation
.
4. Click
Add
.
5. Click
OK
.
■
Ensure that UDP port 44525 is open to communication on the host
computer. If you are using an intelligent switch on the network, ensure that it
is not disabling UDP port 44525.
System Reset
The following figure shows the reset behavior of the cRIO-9066.
Figure 2.
Reset Button Behavior
Press and hold RESET button for
≥
5 s
Press and hold RESET button for
<
5 s
Run Mode
Safe Mode
Press and hold RESET button for
<
5 s
Press and hold RESET button for
≥
5 s
Press and hold
RESET button for
≥
5 s
Press and hold
RESET button for < 5 s
• Console Out enabled
• Network settings reset
• RT Startup App disabled
• FPGA Startup App disabled
• Console Out enabled
• RT Startup App disabled
• FPGA Startup App disabled
Safe Mode
STATUS LED Indicators
The following table describes the STATUS LED indicators.
Table 3.
STATUS LED Indicators
LED Pattern
Indication
Blinks twice and
pauses
The cRIO-9066 is in safe mode. Software is not installed, which is the factory
default state, or software has been improperly installed on the cRIO-9066.
An error can occur when an attempt to upgrade the software is interrupted.
Reinstall software on the cRIO-9066. Refer to the Measurement &
Automation Explorer (MAX) Help for information about installing software
on the cRIO-9066.
Blinks three times
and pauses
The cRIO-9066 is in user-directed safe mode, or the cRIO-9066 is in install
mode to indicate that software is currently being installed.
ni.com
16
cRIO-9066 Getting Started