10. Click
Finish
when the installation is complete.
Troubleshooting the cRIO-9066
The cRIO-9066 is Not Communicating with the Network
■
Ensure that the USB connections between the cRIO-9066 and the host
computer and the Ethernet connections between the host computer and the
router are secure.
■
Configure the IP and other network settings by completing the following
steps.
1. Use a USB A-to-B cable to connect the cRIO-9066 USB device port to a
host computer. The USB driver creates a virtual network interface card
and assigns an IP address to the cRIO-9066 in the format of 172.22.11.x.
2. In MAX, expand your system under Remote Systems.
3. Select the
Network Settings
tab to configure the IP and other network
settings.
4. (Optional) Use the RJ-45 Ethernet port 1 to reconnect the cRIO-9066 to
the host computer. The cRIO-9066 attempts to initiate a DHCP network
connection at powerup.
Note
If the cRIO-9066 cannot obtain an IP address, it connects
to the network with a link-local IP address with the form
169.254.x.x. The host computer communicates with the
cRIO-9066 over a standard Ethernet connection.
■
Ensure that you have the correct version of NI CompactRIO Device Drivers
installed on the host computer. Visit
and enter the Info Code
swsupport for the minimum supported versions of LabVIEW and
NI CompactRIO Device Drivers.
Tip
If you have recently upgraded LabVIEW, you must reinstall NI
CompactRIO Device Drivers.
ni.com
14
cRIO-9066 Getting Started