Have an authorized dealer install the appliance. If you install the appliance yourself, have your dealer review
your installation plans and/or installation.
Draw out a detailed plan of the installation including dimensions and verify the dimensions with the
requirements listed in this manual.
You may wish to adjust the appliance position slightly to ensure the vent does not intersect with a framing
member. Appliance must be positioned so that no combustibles are within, or can swing within (e.g. drapes,
doors), 4 feet (1.2m) of the front of the appliance.
67.1B
!
WARNING
DO NOT INSTALL INTO ANY AREA HAVING A HEIGHT LESS THAN 7 FEET (2.1m)
(CELING OF ENCLOSURE TO APPLIANCE BOTTOM, EXCLUDING HEATH HEIGHT)
3.0 PRE-INSTALLATION PREPARATION
3.1 APPLIANCE PLACEMENT
3.2 CLEARANCE TO COMBUSTIBLES
PARALLEL & CORNER
SINGLE WALL CONNECTOR
DOUBLE WALL CONNECTOR
S1
S4
S9
S1
S4
S9
SIDEWALL (A)
16”
(40.6cm)
16”
(40.6cm)
22”
(55.9cm)
16”
(40.6cm)
16”
(40.6cm)
22”
(55.9cm)
SIDEWALL TO FLUE
18”
(45.7cm)
18”
(45.7cm)
18”
(45.7cm)
*
*
*
BACKWALL (B)
10”
(254mm)
12”
(305mm)
12”
(305mm)
6”
(152mm)
6”
(152mm)
12”
(305mm)
BACKWALL TO FLUE
18”
(45.7cm)
18”
(45.7cm)
18”
(45.7cm)
*
*
*
CORNER (C)
6”
(152mm)
6”
(152mm)
8”
(203mm)
2”
(51mm)
4”
(102mm)
8”
(203mm)
CEILING (D)
7 feet
(2.1m)
7 feet
(2.1m)
7 feet
(2.1m)
7 feet
(2.1m)
7 feet
(2.1m)
7 feet
(2.1m)
Clearances can be reduced with shielding acceptable to local authorities. Reduced installation must comply
with NFPA 211 or CAN/CSA-B365.
BACK WALL
B
SI
D
E
W
A
LL
A
BACK WALL
C
SI
D
E
W
A
LL
F
K
J
J
I
D
E
E
MUR DE L’ARRIÈRE
B
MUR DU CÔTÉ
A
C
MUR DU CÔTÉ
F
D
E
E
MUR DE L’ARRIÈRE
* Double wall connector clearances are as per the connector manufacturer’s instructions.
B
*
C
C
D
*