EN
W415-2007 / A / 10.21.19
21
operation
Draft is the force which moves air from the fi rebox up through the chimney. The amount of draft in the chimney
depends on the length and diameter of the chimney, local geography, nearby obstructions, etc.
Adjusting the air control all the way to the right reduces the temperature. The draft can be adjusted from low to
high by moving the handle from right to left. Inadequate draft may cause back-puffi ng into the room through the
appliance and chimney connector points and may cause plugging of the chimney.
Too much draft may cause the appliance to become too hot. Glowing red appliance parts or chimney connectors,
as well as uncontrollable burns, can lead to chimney fi res or permanent damage to the appliance.
Do not operate the appliance for longer than 30 minutes with the air control on “HIGH” (fully open).
AIR CONTROL
5.3 air
control
5.4 fi re extinguishers / smoke & carbon monoxide detectors
!
WARNING
•
This wood appliance has a manufacturer-set minimum low burn rate that must not be altered. It is against
federal regulations in the United States to alter this setting or otherwise operate this wood appliance in a
manner inconsistent with operating instructions in this manual.
All homes with a solid fuel burning appliance should have at least one fi re extinguisher in a central location,
known to all, at least one smoke detector and carbon monoxide (CO) detector in the room containing the
appliance. If the smoke detector sounds an alarm, correct the cause but do not deactive or relocate the smoke
detector. If the carbon monoxide detector sounds an alarm, immediately vent the area, evacuate and call your
local fi re department.
Always check that smoke and CO detectors are working properly.
note: