6

W415-0153 / A / 10.29.01

HORIZONTAL RUN NOT TO EXCEED VERTICAL RISE

SPECIAL INSTALLATION EXAMPLE

When a horizontal offset is required in a through-the-roof
installation, the following procedure for vent length calcula-
tions must be followed:

In an installation as shown in  

FIGURE 7,

lengths A and C are known based on
room height and roof requirements.

Length C must never be less than 29
inches. Any 90° and 45° elbows must
be calculated as 5 feet of venting
each.

The allowable horizontal run can be cal-
culated using these parameters. In this
example, the total vertical height is 20
feet (length "A" is required to be 11 feet
while length "C" needs to be 9 feet). The
maximum vertical length is 40 feet and
all runs and elbows must be subtracted
from this maximum vertical length.

The maximum allowable horizontal run that "B" can be is:

 40 ft. (maximum vertical run length)

-

11 ft. (through the roof vertical rise 

"A"

)

-10 ft. (2 - 90° elbow)

-  9 ft. (vertical run 

"C"

)

10 ft. (maximum allowable horizontal  length for 

"B"

)

The length of "B" must never be greater than the length
of "A" and "C" combined.

OFFSET INSTALLATION EXAMPLE

FIGS 5

FIGURE 4

If a 

first run of 72 inches 

is re-

quired, using the "First Vent Run"
on the chart shows that a  

maxi-

mum second run of 48 inches

is allowable.

IF  NECESSARY, THE FIRST

RUN AND THE SECOND

RUN MAY BE REVERSED.

R E Q U I R E D
V E R T I C A L
RISE FROM
F I R E P L A C E
TO FIRST EL-
BOW IN
INCHES

FIGURE 6

CALCULATED HORIZONTAL VENT RUN IN FEET

For optimum flame appearance and stove performance,
keep the vent length and number of elbows to a minimum.
The air terminal must remain unobstructed at all times.
Examine the air terminal at least once a year to verify that it
is unobstructed and undamaged.

The maximum horizontal run is 34 inches with a 90° elbow
located 29" above the stove. 

FIGURE 4.

The maximum horizontal run with a 57 inch vertical rise
immediately above the stove is 20 feet 

. Figures 5.

If  vertical rises greater than 57 inches are necessary,
the increased rise must be deducted from the maxi-
mum horizontal run.

Use chart, 

Figure 6,

 to calculate horizontal runs for vertical

rises between 29 and 57 inches.

When calculating maximum run lengths, include 10 feet
for each 90° elbow or 5 feet for each 45° elbow.

Do not include the first elbow directly off the unit.

FIGURE 8

  57"

first run

72"

second run

48" 

FIGURE 9

C

B

A

FIGURE 7

Summary of Contents for Haliburton GDS28N

Page 1: ...ada L4M 4Y8 705 721 1212 R 2000 Installation and service must be performed by a qualified installer service agency or the gas supplier WARNING If the information in these instructions is not followed...

Page 2: ...uld stay away to avoid burns or clothing ignition Supervise young children when they are in the same room as the stove Due to high temperatures the stove should be located out of traffic and away from...

Page 3: ...Labour costs to the however requires the prior approval of an authorized company official Labour costs to the account of account of account of account of account of NAPOLEON NAPOLEON NAPOLEON NAPOLEON...

Page 4: ...aler Do not substitute materials Clean the glass after the first 10 hours of operation with a recommended gas fireplace glass cleaner Thereafter clean as required Do not clean glass when hot If the gl...

Page 5: ...VENTING LENGTHS AND AIR TERMI NAL LOCATIONS Use only Wolf Steel or Simpson Dura Vent Model DV GS venting components Minimum and maximum vent lengths for both horizontal and vertical installations and...

Page 6: ...d OFFSET INSTALLATION EXAMPLE FIGS 5 FIGURE4 If a first run of 72 inches is re quired using the First Vent Run on the chart shows that a maxi mum second run of 48 inches is allowable IF NECESSARY THE...

Page 7: ...EET Clearance above grade veranda porch deck or balcony Clearance to windows or doors that open Clearance to permanently closed windows Vertical clearance to ventilated soffit located above the termin...

Page 8: ...sition apply sealant between the pipe and the firestop spacer 3 In the attic after the pipe has been installed slide the vent pipe collar down to cover up the open end of the shield and tighten This w...

Page 9: ...rain cap 7 In the attic slide the vent pipe collar down to cover up the open end of the shield and tighten This will prevent any materials such as insulation from filling up the 1 air space around the...

Page 10: ...e base For mobile home installations the fireplace must be fastened in place Use 10 screws inserted through the holes in the base to se cure It is recommended that the fireplace be secured in all inst...

Page 11: ...ew the wire access cover plate from the rear right hand side of the firebox Remove and discard the gasket SEE FIGURE 25 Remove the knockout from the cover plate and insert the protective bushing Pull...

Page 12: ...of or building within 10 feet FIGURE 26 This is a guideline only local venting codes should be followed which may differ in height and clearance requirements Continue with Gas Installation Page 13 INS...

Page 13: ...IES TO CANADA ONLY L EFFICACITE CONSTANTE S APPLIQUENT SEULEMENT AU CANADA AFUE NG LP GN GP 64 65 MINIMUM AND MAXIMUM HORIZONTAL VENT LENGTHS ARE 25 INCHES AND 20 FEET RESPECTIVELY LES LONGUEURS HORIZ...

Page 14: ...close to the firebox wall as possible and centered onto the log support pan FIGURES 31 FIGURES 30 Place the front log on the ember screen lining up the studs with the holes on the bottom of the log CA...

Page 15: ...n MODEL GS28 ONLY SPILL SWITCH This is a thermally activated switch attached to the back of the chimney adapter which senses the change in temperature and shuts down the gas valve in the event of a se...

Page 16: ...servicing the stove CAUTION Label all wires prior to disconnection when serv icing controls Wiring errors can cause improper and dan gerous operation Verify proper operation after servicing This stove...

Page 17: ...neither pinched nor interfere with the blower operation Re se cure the air intake manifolds INSTALLATION THROUGH THE FIRE BOX Replacement blower access gasket is required 2 Open the lower control door...

Page 18: ...el plate To access the venturi remove the air housing cover plate held on with 2 screws Take care not to damage the gasket Natural gas and propane models have air shutters set fully open Closing the a...

Page 19: ...ABLE PIPE 7 DIA W500 0077 FIRESTOP WALL PLATE W020 0032 HARDWARE BRTC7 BRASS TRIM COLLAR BM6724 24 STOVE PIPE 7 DIAMETER W010 0300 10 ALUMINIUM FLEX LINER C W SPACERS 4 DIA W025 0001 DECORATIVE BRASS...

Page 20: ...ARIABLE SPEED SWITCH GZ 552 REPLACEMENT BLOWER W030 0022 ACCENT BAR W200 0077 BLACK TRIVET GS28 W010 0459 ADAPTOR C W SPILL SWITCH W660 0006 SPILL SWITCH ACCESSORIES OPTIONS GDS28 GS28 W690 0001 MILLI...

Page 21: ...standing Main burner is in OFF position turn on all gas appliances and see if pilot flame flutters diminishes or extinguishes especially when main burner ig nites Monitor supply pressure check if supp...

Page 22: ...location of storm collars Incorrect installation Carbon is being de posited on glass logs or combustion chamber surfaces Flame is impinging on the logs or combustion chamber check that the logs are co...

Page 23: ...23 W415 0153 A 10 29 01 Wolf Steel Fireplace Service History This fireplace must be serviced annually depending on usage Date Service Technician Name Service Performed Special Concerns Dealer Name...

Page 24: ...24 W415 0153 A 10 29 01 NOTES...

Reviews: